CONSTRUCTION | |
Conductor: | - Class B compressed concentric stranded bare copper |
Conductor Shield: | - Extruded semi-conducting thermosetting polymeric layer |
Insulation: | - Ethylene polypropylene rubber type EPR - 133% insulation level, semiconducting insulation shield / insulation thickness of .220" |
Insulation Shield: | - 5 mil copper tape |
Assembly: | - The insulated and shielded power conductors shall be cabled round with fillers and with a grounding conductor in one outer interstice and covered with a binder tape. |
Armor: | - A single strip of aluminum interlocked armor |
Jacket: | - Red PVC jacket - Flame and sunlight resistant |
Applications:
- For use in aerial installations, direct burial, metal racks, open trays, troughs, or continuous rigid cable supports
- Rated at 15kV, 133% insulation level (underground system)
- Operates continuously at a maximum temperature of 105°C for normal operations, 140°C for emergency overload operations, and 250°C for short circuit conditions.
Standards:
- Rated at 15kV, 133% insulation level (underground system)
- Operates continuously at a maximum temperature of 105°C for normal operations, 140°C for emergency overload operations, and 250°C for short circuit conditions.
- UL 1072
- IEEE 1202 (70,000 BTU), CSA/FT4
- ICEA T-29-520 (210,000 BTU)
- IEEE 383 (210,000 BTU)
- ICEA S-93-639 / NEMA WC-74
- IEEE 1202 (70,000 BTU), CSA/FT4
- ICEA T-29-520 (210,000 BTU)
- IEEE 383 (210,000 BTU)
- ICEA S-93-639 / NEMA WC-74
Part # | AWG Size | No. of Cond. | Grd. Size | Nom. Jacket Thick | Nom. O.D. | Lbs./M’ | Ampacity * / + |
|
Armor | Overall | |||||||
1Y30203A | 2 | 3 | 6 | .060” | 2.26” | 2.41” | 2506 | 200/185 |
1Y30103A | 1 | 3 | 4 | .075” | 2.35” | 2.52” | 2775 | 225/210 |
1Y31/003A | 1/0 | 3 | 4 | .075” | 2.43” | 2.61” | 3177 | 255/240 |
1Y32/003A | 2/0 | 3 | 4 | .075” | 2.53” | 2.70” | 3554 | 290/275 |
1Y33/003A | 3/0 | 3 | 3 | .075” | 2.64” | 2.81” | 4014 | 330/315 |
1Y34/003A | 4/0 | 3 | 3 | .075” | 2.76” | 2.93” | 4617 | 375/360 |
1Y325003A | 250 | 3 | 3 | .075” | 2.93” | 3.10” | 5177 | 410/400 |
1Y335003A | 350 | 3 | 2 | .085” | 3.14” | 3.34” | 6590 | 495/490 |
1Y350003A | 500 | 3 | 1 | .085” | 3.42” | 3.62” | 8385 | 590/600 |
1Y360003A | 600 | 3 | 1 | .085” | 3.47” | 3.64” | 8864 | 600 |
1Y375003A | 750 | 3 | 1/0 | .085” | 3.69” | 3.86” | 11081 | 670 |
* Direct burial ampacities are based on Table 310-83 three conductors within an overall covering directly buried, 90°C conductor, 20°C earth ambient temperature.
+ In air ampacities are based on 310-71 three conductors within an overall covering in free air, 90°C conductor, 40°C ambient temperature.