CONSTRUCTION | |
Conductor: | - Class B stranded, bare copper in accordance with ASTM B3 and B8 |
Conductor Shield: | - Extruded semi-conducting thermosetting polymeric layer firmly bonded to the insulation |
Insulation: | - XLP (Cross linked thermosetting polyethylene) with average thickness of .115" meeting the requirements of the referenced standards |
Insulation Shield: | - Shielded with an extruded semi-conducting thermosetting polymeric layer using printed circuit numbers and colors |
Grounding Conductor: | - Class B stranded bare copper in accordance with ASTM B3 and B8 |
Assembly: | - The insulated and shielded power conductors will be cabled round with fillers and with a grounding conductor in one outer interstice and covered with a binder tape. |
Armor: | - Aluminum interlocked armor |
Jacket: | - Flame and sunlight resistant yellow PVC jacket |
Applications:
- For use in aerial installations, direct burial, metal racks, open trays, troughs, or continuously rigid cable supports.
- Capable of operating continuously at a maximum conductor temperature of 90°C for normal operations, 130°C for emergency operations, and 250°C for short circuit conditions.
Standards:
- Capable of operating continuously at a maximum conductor temperature of 90°C for normal operations, 130°C for emergency operations, and 250°C for short circuit conditions.
- UL 1072
- UL Type MV-90
- IEEE-1202 (70,000 BTU) and ICEA T-29-520 (210,000 BTU)
- UL Type MV-90
- IEEE-1202 (70,000 BTU) and ICEA T-29-520 (210,000 BTU)
Part # | AWG Size | Ground AWG | Nom. Jacket Thick | Nom. O.D. | Lbs./M’ | Ampacity */+ |
|
Armor | Jacket | ||||||
1Y41/003 | 1/0 | 4 | .060” | 1.56” | 1.69” | 1855 | 185/230 |
1Y42/003 | 2/0 | 4 | .060” | 1.65” | 1.78” | 2175 | 215/260 |
1Y43/003 | 3/0 | 4 | .060” | 1.79” | 1.92” | 2700 | 250/295 |
1Y44/003 | 4/0 | 3 | .060” | 1.91” | 2.03” | 3230 | 285/335 |
1Y425003 | 250 | 3 | .060” | 2.02” | 2.15” | 3655 | 320/365 |
1Y435003 | 350 | 2 | .075” | 2.24” | 2.37” | 4795 | 395/440 |
1Y450003 | 500 | 1 | .075” | 2.51” | 2.68” | 6535 | 485/530 |
1Y475003 | 750 | 1/0 | .085” | 2.91” | 3.07” | 9245 | 615/650 |
* Ampacity for cable in air-conductor temperature of 90°C and ambient temperature of 40°C.
+ Ampacity for cable direct burial with 90°C conductor temperature and 20°C earth temperature.