CONSTRUCTION | |||||||||||||||||||||||||||||
Conductor: | - Stranded, bare copper in accordance with ASTM B3 and B8 | ||||||||||||||||||||||||||||
Insulation: | - Cross-linked polyethylene type XHHW-2 per UL44 | ||||||||||||||||||||||||||||
Ground Wire: | - Class B stranded bare copper in accordance with ASTM B3 and B8 | ||||||||||||||||||||||||||||
Assembly: | - Conductors are cabled with suitable fillers and bare copper ground conductor - Cable core is covered with binder tape |
||||||||||||||||||||||||||||
Armor: | - Aluminum interlocked armor | ||||||||||||||||||||||||||||
Color Code Chart 107 (Y11203A & Y11003A): |
|
||||||||||||||||||||||||||||
Color Code Chart 108 (All Others): |
|
||||||||||||||||||||||||||||
Jacket: | - Flame and sunlight resistant black PVC jacket |
Standards:
- UL 1569, UL 44, UL 1581, UL Type MC-600 volts
- ICEA S-95-658/NEMA WC 70, ICEA T-29-520
- NEC Type XHHW-2 conductors
- IEEE 383, IEEE 1202
- Meets EPA 40 CFR part 261
- OSHA acceptable, NEC
Applications:
- ICEA S-95-658/NEMA WC 70, ICEA T-29-520
- NEC Type XHHW-2 conductors
- IEEE 383, IEEE 1202
- Meets EPA 40 CFR part 261
- OSHA acceptable, NEC
- Designed for use on power or control circuits
- Can be installed in cable tray, wire ways, racks, or buried directly
- Permitted for use in Class I, Division II and Class II, Division II per NEC
- Can be installed in cable tray, wire ways, racks, or buried directly
- Permitted for use in Class I, Division II and Class II, Division II per NEC
Part # | AWG Size | No. of Cond. | Nom. Insul. Thick. | Ground Wire Size | Nom. O.D. | Lbs./M’ | Ampacity* 40°C Ambient | Recommend Fitting | |
Armor | Overall | ||||||||
Y11203A | 12 | 3 | .030” | 12 | .54” | .65” | 215 | – | STE050 |
1Y11003A | 10 | 3 | .030” | 10 | .61” | .73” | 300 | – | STE050 |
1Y10803A | 8 | 3 | .045” | 10 | .75” | .85” | 410 | 55 | STE050 |
1Y10603A | 6 | 3 | .045” | 8 | .83” | .93” | 551 | 75 | STE075 |
1Y10403A | 4 | 3 | .045” | 8 | .92” | 1.03” | 727 | 95 | STE100 |
Y10203A | 2 | 3 | .045” | 6 | 1.05” | 1.15” | 1050 | 130 | STE125 |
1Y10103A | 1 | 3 | .055” | 6 | 1.23” | 1.33” | 1283 | 150 | STE125 |
1Y11/003A | 1/0 | 3 | .055” | 6 | 1.33” | 1.43” | 1553 | 170 | STE125 |
1Y12/003A | 2/0 | 3 | .055” | 6 | 1.43” | 1.53” | 1859 | 195 | STE150 |
1Y13/003A | 3/0 | 3 | .055” | 4 | 1.55” | 1.67” | 2314 | 225 | STE150 |
1Y14/003A | 4/0 | 3 | .055” | 4 | 1.67” | 1.79” | 2781 | 260 | STE150 |
1Y125003A | 250 | 3 | .065” | 4 | 1.81” | 1.93” | 3356 | 290 | STE200 |
1Y135003A | 350 | 3 | .065” | 3 | 2.05” | 2.17” | 4485 | 350 | STE200 |
1Y150003A | 500 | 3 | .065” | 2 | 2.33” | 2.48” | 6204 | 430 | STE250 |
1Y160003A | 600 | 3 | .080” | 2 | 2.57” | 2.72” | 7321 | 475 | STE300 |
1Y175003A | 750 | 3 | .080” | 1 | 2.85” | 3.00” | 9062 | 535 | STE300 |
*Ampacity per NEC Table 310-16