CONSTRUCTION | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Conductor: | - Bare, annealed copper conforming to ASTM B-3 and stranded in accordance with ASTM B8 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Insulation: | - Cross-linked polyethylene type XHHW-2 per UL 44 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Grounding Conductor: | - Class B stranded bare copper per ASTM B3 and B8 - Cross-linked polyethylene (XLPE) insulation, green - Sized in accordance with NEC Table 250.122 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Assembly: | - Conductors are cabled in concentric layers with grounding wire, interstices are filled with suitable non-hygroscopic fillers, as required. - A binder tape of synthetic material assembles the core in an essentially round configuration. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Armor: | - Continuous corrugated aluminum sheath 99.5% is applied over the assembly. The continuous sheath will be impervious to moisture, liquids, and gases. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Color Code ICEA Method 1, Table E2: |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Jacket: | - Black polyvinyl chloride (PVC), sunlight and oil resistant, per UL 1569, 90°C temperature rating. |
Applications:
- Designed for use on power or control circuits
- Can be installed in cable tray, wire ways, racks, or buried directly
- Suitable for exposure to hazardous locations, Type MC-HL for Classes I, II, and III Division 1 and 2
Standards:
- Can be installed in cable tray, wire ways, racks, or buried directly
- Suitable for exposure to hazardous locations, Type MC-HL for Classes I, II, and III Division 1 and 2
- UL 44, XHHW-2 600 Volt conductors
- UL 1569 Type MC and UL 2225 Type MC-HL
- Designated Type MC as per NEC Article 334
- Passes UL and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEC 332-3 category A fire test, IEEE 1202, and CSA FT4
- UL 1569 Type MC and UL 2225 Type MC-HL
- Designated Type MC as per NEC Article 334
- Passes UL and IEEE 383 vertical tray fire tests at 70,000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEC 332-3 category A fire test, IEEE 1202, and CSA FT4
Part # | AWG Size | No. of Cond. | Grd. Size | Nom. O.D. | Lbs./M’ | Recommended Fitting | |
Armor | Overall | ||||||
1X11403 | 14 | 3 | 14 | .530” | .640” | 192 | STX050464 |
1X11404 | 14 | 4 | 14 | .580” | .690” | 222 | STX050464 |
1X11405 | 14 | 5 | 14 | .600” | .710” | 245 | STEX075 |
1X11406 | 14 | 6 | 14 | .620” | .730” | 267 | STEX075 |
1X11408 | 14 | 8 | 14 | .710” | .820” | 321 | STEX100 |
1X11409 | 14 | 9 | 14 | .740” | .850” | 377 | STEX100 |
1X11411 | 14 | 11 | 14 | .800” | .910” | 395 | STEX100 |
1X11418 | 14 | 18 | 14 | .930” | 1.04” | 554 | STEX100 |
1X11436 | 14 | 36 | 14 | 1.24” | 1.35” | 948 | STEX100 |
1X11437 | 14 | 37 | 14 | 1.22” | 1.32” | 1030 | STEX125 |
1X11202 | 12 | 2 | 12 | .530” | .640” | 200 | STX050464 |
1X11203 | 12 | 3 | 12 | .580” | .690” | 239 | STX050464 |
1X11204 | 12 | 4 | 12 | .670” | .780” | 310 | STX050464 |
1X11205 | 12 | 5 | 12 | .670” | .780” | 324 | STX050464 |
1X11206 | 12 | 6 | 12 | .670” | .780” | 338 | STX050464 |
1X11207 | 12 | 7 | 12 | .710” | .820” | 408 | STX050464 |
1X11208 | 12 | 8 | 12 | .800” | .910” | 426 | STEX100 |
1X11211 | 12 | 11 | 12 | .890” | 1.00” | 519 | STEX100 |
1X11212 | 12 | 12 | 12 | .885” | .995” | 584 | STEX100 |
1X11218 | 12 | 18 | 12 | 1.02” | 1.13” | 739 | STEX100 |
1X11236 | 12 | 36 | 12 | 1.37” | 1.48” | 1302 | STEX150 |
1X11002 | 10 | 2 | 10 | .580” | .690” | 253 | STX050464 |
1X11003 | 10 | 3 | 10 | .620” | .730” | 303 | STX050464 |
1X11004 | 10 | 4 | 10 | .670” | .780” | 348 | STEX075 |
X11006 | 10 | 6 | 10 | .750” | .860” | 451 | STEX075 |
1X11008 | 10 | 8 | 10 | .890” | 1.00” | 568 | STEX075 |
1X11011 | 10 | 11 | 10 | .970” | 1.08” | 704 | STEX100 |
*Ampacities are in accordance with Table 310-16 of NEC.