CONSTRUCTION | |||||||||||||||||||||||||
Conductor: | - Bare, annealed copper conforming to ASTM B-3 and stranded in accordance with ASTM B8. | ||||||||||||||||||||||||
Insulation: | - Cross-linked polyethylene type XHHW per UL 44. | ||||||||||||||||||||||||
Grounding Conductors: | - Class B stranded bare copper per ASTM B3 & B8 - Sized in accordance with NEC Table 250.122 |
||||||||||||||||||||||||
Assembly: | - Conductors are cabled in concentric layers with grounding wire, interstices are filled with suitable non-hygroscopic fillers, as required. - A binder tape of synthetic material is applied over the cabled core. |
||||||||||||||||||||||||
Armor: | - Impervious, continuously welded and corrugated aluminum alloy sheath | ||||||||||||||||||||||||
Jacket: | - Black polyvinyl chloride (PVC), sunlight and oil resistant, per UL 1569, 90°C temperature rating. | ||||||||||||||||||||||||
Color Code: | - 6 AWG & smaller: M1, E2 - 4 AWG & larger: M4
|
Standards:
- UL 44, XHHW-2 600V conductors
- Designated Type MC as per NEC Article 334
- UL 1569 Type MC and UL 2225 Type MC-HL
- Passes UL and IEEE 383 vertical tray fire tests at 70,0000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEC 332-3 category A fire test, IEEE1202 and CSA FT4
Applications:
- Designated Type MC as per NEC Article 334
- UL 1569 Type MC and UL 2225 Type MC-HL
- Passes UL and IEEE 383 vertical tray fire tests at 70,0000 BTU/hr, ICEA T-29-520 fire test at 210,000 BTU/hr, IEC 332-3 category A fire test, IEEE1202 and CSA FT4
- Designed for use on power or control circuits
- Can be installed in cable tray, wire ways, racks, or buried directly
- This cable has three symmetrically placed grounds to reduce problems associated with pulse - width modulated AC drives. Suitable for VFD applications.
- Suitable for exposure to hazardous locations, Type MC-HL for Classes I, II, and III Division 1 and 2
- Can be installed in cable tray, wire ways, racks, or buried directly
- This cable has three symmetrically placed grounds to reduce problems associated with pulse - width modulated AC drives. Suitable for VFD applications.
- Suitable for exposure to hazardous locations, Type MC-HL for Classes I, II, and III Division 1 and 2
Part # | AWG Size | No. of Cond. | Ground No. x AWG | Nom. O.D. | Lbs./M’ | Recommended Fitting | |
Armor | Overall | ||||||
1X21403 | 14 | 3 | 3 × 18 | .530” | .640” | 163 | STEX075 |
1X21404 | 14 | 4 | 3 × 18 | .580” | .690” | 226 | STEX075 |
1X21203 | 12 | 3 | 3 × 16 | .580” | .690” | 243 | STEX075 |
1X21204 | 12 | 4 | 3 × 16 | .670” | .780” | 291 | STEX075 |
1X21003 | 10 | 3 | 3 × 14 | .620” | .730” | 305 | STEX075 |
1X21004 | 10 | 4 | 3 × 14 | .670” | .780” | 354 | STEX075 |
1X20803 | 8 | 3 | 3 × 14 | .710” | .810” | 392 | STEX075 |
1X20603 | 6 | 3 | 3 × 12 | .800” | .900” | 534 | STEX075 |
X20403 | 4 | 3 | 3 × 12 | .890” | .990” | 716 | STEX100 |
1X20203 | 2 | 3 | 3 × 10 | 1.02” | 1.27” | 1013 | STEX150 |
1X20103 | 1 | 3 | 3 × 10 | 1.15” | 1.26” | 1119 | STEX150 |
1X21/003 | 1/0 | 3 | 3 × 10 | 1.24” | 1.34” | 1496 | STEX150 |
1X22/003 | 2/0 | 3 | 3 × 10 | 1.34” | 1.44” | 1801 | STEX200 |
1X23/003 | 3/0 | 3 | 3 × 8 | 1.47” | 1.58” | 2262 | STEX200 |
1X24/003 | 4/0 | 3 | 3 × 8 | 1.60” | 1.73” | 2722 | STEX250 |
1X225003 | 250 | 3 | 3 × 8 | 1.74” | 1.87” | 3195 | STEX250 |
1X235003 | 350 | 3 | 3 × 7 | 1.96” | 2.09” | 4284 | STEX250 |
1X250003 | 500 | 3 | 3 × 6 | 2.28” | 2.44” | 6035 | STEX300 |
1X275003 | 750 | 3 | 3 × 5 | 2.75” | 2.92” | 8854 | – |
*Ampacities are in accordance with Table 310-16 of NEC.