CONSTRUCTION | |
Conductor: | - Bare, annealed copper conforming to ASTM B3 and stranded in accordance with ASTM B8 (Class B) |
Insulation: | - Flame-retardant PVC insulation and nylon covering, rated 90°C per UL Standard 83 - Color Code: ICEA Method 1 |
Overall Shield: | - Aluminum/polyester tape shield providing 100% coverage - Stranded tinned copper drain wire, same size as insulated conductors |
Inner Jacket: | - Flame retardant PVC per UL 1569, Black - Low temp performance meets ASTM D746 brttleness temp at or below -40°C - Nylon ripcord |
Armor: | - Impervious, continuously corrugated and welded aluminum per UL 1569 & 2225 - Meets grounding requirements of NEC Article 250 |
Overall Jacket: | - Flame-retardant, moisture and sunlight resistant PVC per UL Standards 1569, black - Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C |
Applications:
- For use in Class 1 remote-control and signal circuits in accordance with NEC Article 725
- Recognized for use in Class I, II, and III, Divisions 1 and 2; or Class I, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503 and 505.
- Installed indoors or outdoors, in wet or dry locations, in a raceway, as aerial cable on a messenger, in cable trays , or for direct burial
- Recognized for use on fixed or floating offshore petroleum facilities as recommended by American Petroleum Institute.
Features:
- Recognized for use in Class I, II, and III, Divisions 1 and 2; or Class I, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503 and 505.
- Installed indoors or outdoors, in wet or dry locations, in a raceway, as aerial cable on a messenger, in cable trays , or for direct burial
- Recognized for use on fixed or floating offshore petroleum facilities as recommended by American Petroleum Institute.
- CCW provides EMI shielding performance
- Meets cold impact at -40°C
- Meets cold impact at -40°C