CONSTRUCTION | |||||||||||||
Conductor: | - Annealed bare copper - Class B stranding in accordance with ASTM B8 - In sizes 8 AWG to 1000 kcmil, the conductors may be compact stranded to reduce cable diameter and weight |
||||||||||||
Insulation: | - Cross linked polyethylene, rated CSA C22.2 No. 38 type RW90 | ||||||||||||
Assembly: | - Cabled in concentric layers with grounding wire, interstices are filled with suitable nonhygroscopic fillers, as required - A binder tape of synthetic material assembles the core in an essentially round configuration, as required |
||||||||||||
Inner Jacket: | - Black polyvinyl chloride jacket | ||||||||||||
Armor: | - Interlocking aluminum tape armor applied over inner jacket | ||||||||||||
Outer Jacket: | Black polyvinyl chloride jacket | ||||||||||||
Color Code: | - 4 Conductors or less use the color code chart below
|
Applications:
- Suitable for use in ventilated, non-ventilated and ladder cable trays, direct earth burial or raceways, and for exposed or concealed wiring in wet, damp or dry locations
- Suitable for use in wet or dry locations when installed in accordance with the NEC
Standards:
- Suitable for use in wet or dry locations when installed in accordance with the NEC
- Meets the requirements of CSA C22.2 No. 38 type RW90 for unshielded conductors and CSA C68.3-97 for shielded conductors
- Meets CSA C22.2 No. 131
Features:
- Meets CSA C22.2 No. 131
- CSA listed as Type Teck
- Suitable for direct burial and use in cable tray
- CSA FT1 & FT4
- 90;deg&C wet or dry, -40;deg&C low temp
- Jacket is sunlight resistant
- Suitable for use in all hazardous locations when used with certified HL cable glands
- Suitable for direct burial and use in cable tray
- CSA FT1 & FT4
- 90;deg&C wet or dry, -40;deg&C low temp
- Jacket is sunlight resistant
- Suitable for use in all hazardous locations when used with certified HL cable glands
Part # | AWG Size | No. of Cond. | Nom. Insul. Thick. | Nom. O.D. | Lbs./M’ | Ground AWG | Recommended Fitting for Standard Locations | Recommended Fitting for Hazardous Locations | ||
Armor | Overall | |||||||||
600V, 10 AWG | ||||||||||
1T31002 | 10 | 2 | 30 mils | .670” | .750” | 276 | 12 | STE050 | STX050464 | |
1T31003 | 10 | 3 | 30 mils | .700” | .780” | 317 | 12 | STE050 | STEX075 | STEX075 |
1T31004 | 10 | 4 | 30 mils | .740” | .830” | 382 | 12 | STE050 | STEX075 | |
1T31006 | 10 | 6 | 30 mils | .880” | .960” | 515 | 12 | STE050 | STEX075 | |
1T31008 | 10 | 8 | 30 mils | .930” | 1.02” | 637 | 12 | STE075 | STEX100 | |
1T31012 | 10 | 12 | 30 mils | 1.150” | 1.230” | 916 | 12 | STE150 | STEX125 | |
600V, 12 AWG | ||||||||||
1T31202 | 12 | 2 | 30 mils | .620” | .700” | 220 | 14 | STE050 | STX050464 | |
1T31203 | 12 | 3 | 30 mils | .650” | .730” | 259 | 14 | STE050 | STX050464 | |
1T31204 | 12 | 4 | 30 mils | .690” | .770” | 290 | 14 | STE050 | STEX075 | |
1T31205 | 12 | 5 | 30 mils | .730” | .810” | 412 | 14 | STE050 | STEX075 | |
1T31207 | 12 | 7 | 30 mils | .830” | .910” | 439 | 14 | STE050 | STEX075 | |
1T31212 | 12 | 12 | 30 mils | 1.01” | 1.10” | 643 | 14 | STE075 | STEX100 | |
600V, 14 AWG | ||||||||||
1T31402 | 14 | 2 | 30 mils | .580” | .670” | 190 | 14 | STE050 | STX050464 | |
1T31403 | 14 | 3 | 30 mils | .600” | .690” | 218 | 14 | STE050 | STX050464 | |
1T31404 | 14 | 4 | 30 mils | .640” | .720” | 246 | 14 | STE050 | STX050464 | |
1T31405 | 14 | 5 | 30 mils | .680” | .760” | 276 | 14 | STE050 | STX050464 | |
1T31407 | 14 | 7 | 30 mils | .740” | .820” | 329 | 14 | STE050 | STEX075 | |
1T31410 | 14 | 10 | 30 mils | .880” | .960” | 450 | 14 | STE050 | STEX075 | |
1T31412 | 14 | 12 | 30 mils | .900” | .990” | 492 | 14 | STE075 | STEX100 | |
1T31415 | 14 | 15 | 30 mils | .960” | 1.04” | 550 | 14 | STE075 | STEX100 | |
1T31420 | 14 | 20 | 30 mils | 1.13” | 1.21” | 745 | 14 | STE100 | STEX125 | |
1T31425 | 14 | 25 | 30 mils | 1.22” | 1.30” | 919 | 14 | STE100 | STEX125 |