CONSTRUCTION | |
Conductor: | - 14 AWG fully annealed stranded copper per ASTM B33 - Class B stranding per ASTM B8. |
Insulation: | - Cross-Linked Polyolefin (XLPO), flame retardant and Low-Smoke - Color Code: Table E-2, no white or green |
Jacket: | - Low-Smoke, Zero halogen Polyolefin - Flame retardant and Sunlight resistant. |
Application:
- In free air, raceways, aerial or direct burial
- In wet or dry locations
- Class 1 Division 2
- Permitted for Exposed Runs in three or more conductors
Compliances:
- In wet or dry locations
- Class 1 Division 2
- Permitted for Exposed Runs in three or more conductors
- UL 44 Type XHHW-2
- UL 1277 Type TC-LS-ER
- UL 1581
- UL 1685
- ROHS Compliant
- OSHA acceptable
- EPA 40 CFR, Part 261
- UL 1277 Type TC-LS-ER
- UL 1581
- UL 1685
- ROHS Compliant
- OSHA acceptable
- EPA 40 CFR, Part 261
Part # | AWG | No. of Cond. | Nom. Jkt. Thickness | Nominal O.D. | Lbs./M’ | T&B Fitting |
1AZ11402F* | 14 | 2 – flat | 0.045” | .365 x .323” | 61 | - |
1AZ11403 | 14 | 3 | 0.045” | 0.390” | 92 | TCF07540A |
1AZ11404 | 14 | 4 | 0.045” | 0.425” | 115 | TCF05054A |
1AZ11405 | 14 | 5 | 0.045” | 0.465” | 139 | TCF05054A |
1AZ11407 | 14 | 7 | 0.045” | 0.505” | 173 | TCF05054A |
1AZ11409 | 14 | 9 | 0.060” | 0.620” | 240 | TCF05067A |
1AZ11412 | 14 | 12 | 0.060” | 0.700” | 301 | TCF07578A |
1AZ11419 | 14 | 19 | 0.060” | 0.815” | 468 | TCF10088A |
*Approved for -ER for Exposed Run applications of three (3) or more conductors
* Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager.