TRAY CABLE, FREP®* - XHHW - 2 - (VW-1) - 90°
FR-EP Insulation - CPE Jacket
600 Volt - UL Type TC-ER - 3 Conductor w/Ground


CONSTRUCTION
Conductor: - Stranded soft drawn tinned copper, Class B
Insulation: - Flame-retardant ethylene-propylene-rubber meeting the requirements for EPR VW-1 per UL
Assembly: - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary.
- A binder tape (when required) of synthetic material assembles the core in a tight circular configuration
Color Code Chart 108:
Cond. Num. Cond. Marking Cond. Num. Cond. Marking
1 "1" One 2 "2" Two
3 "3" Three 4 "4" Four
Jacket: - Black sunlight resistant thermoplastic Chlorinated Polyethylene (CPE)
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial and for Class 1 Division 2 hazardous locations as per NEC
Standards:
- UL Type TC 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-95-658/NEMA WC70
- ICEA T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr)/CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
Part # AWG Size No. of Cond. Grd. Size Nom. Insul. Thick. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
1AF30803 8 3 10 .045” .060” .657” 359 TCF05067A
1AF30603 6 3 8 .045” .060” .739” 513 TCF05078A
1AF30403 4 3 8 .045” .080” .880” 721 TCF07588A
1AF30203 2 3 6 .045” .080” 1.01” 1063 TCF125109A
1AF30103 1 3 6 .055” .080” 1.15” 1190 TCF125128A
1AF31/003 1/0 3 6 .055” .080” 1.23” 1528 TCF125128A
1AF32/003 2/0 3 6 .055” .080” 1.32” 1830 TCF125147A
1AF33/003 3/0 3 4 .055” .080” 1.42” 2500 TCF125147A
1AF34/003 4/0 3 4 .055” .080” 1.55” 2768 TCF150165A
1AF325003 250 3 4 .065” .110” 1.78” 3298 TCF200186A
1AF335003 350 3 3 .065” .110” 2.00” 3643 TCF200219A
1AF350003 500 3 2 .065” .110” 2.29” 6116 4-300TC
1AF375003 750 3 1 .080” .140” 2.81” 9101 4-350TC
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.