CONSTRUCTION | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Conductor: | - Stranded soft drawn tinned copper, Class B | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Insulation: | - Flame retardant ethylene propylene rubber meeting the requirements for EPR VW-1 per UL | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Assembly: | - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary - A binder tape (when required) of synthetic material assembles the core in a tight circular configuration |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Color Code Chart 107: |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Jacket: | - Black sunlight resistant thermoplastic Chlorinated Polyethylene (CPE) |
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
Standards:
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
- UL Type TC 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-95-658 / NEMA WC70
- ICEA-T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-95-658 / NEMA WC70
- ICEA-T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
Part # | AWG Size | No. of Cond. | Nom. Jacket Thick. | Nom. O.D. | Lbs./M’ | Recommended Fitting |
1AF11002F* | 10 | 2 Flat | .045” | .445” x .270” | 113 | - |
1AF11002* | 10 | 2 | .045” | .455” | 128 | TCF05054A |
1AF11003 | 10 | 3 | .045” | .485” | 172 | TCF05054A |
1AF11004 | 10 | 4 | .060” | .560” | 234 | TCF05067A |
1AF11005 | 10 | 5 | .060” | .615” | 284 | TCF05067A |
1AF11007 | 10 | 7 | .060” | .670” | 381 | TCF05067A |
1AF11009 | 10 | 9 | .060” | .785” | 488 | TCF07588A |
1AF11012 | 10 | 12 | .080” | .920” | 651 | TCF100100A |
1AF11015 | 10 | 15 | .080” | 1.02” | 810 | TCF125109A |
1AF11019 | 10 | 19 | .080” | 1.08” | 967 | TCF125109A |
1AF11024 | 10 | 24 | .080” | 1.36” | 1221 | TCF125147A |
1AF11037 | 10 | 37 | .080” | 2.10” | 1885 | TCF200219A |
*ER Rating only applies to 3 conductors or more