CONSTRUCTION | |
Conductor: | - Aluminum alloy 1350 Class B concentric compressed strand |
TR-XLP Insulation: | - Natural unfilled high dielectric strength tree-retardant cross-linked polyethylene(TR-XLP)insulation, exhibiting an optimum balance of mechanical and electrical properties assuring cable life and resistance to treeing |
Neutral Conductor: | - Solid, bare annealed uncoated copper wires helically applied and uniformly spaced. Conductance equivalent to 100% of main(power)conductor. |
Insulation Shield: | - Semiconducting extruded thermosetting insulation shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping |
Jacket: | - Black sunlight linear low density polyethylene encapsulating the neutral wires - The outer jacket shall have three extruded red stripes(120 degrees apart) for identification |
Applications:
- For use in underground residential distribution, as primary power cable in single-phase systems direct buried or underground in duct
Features:
- Simultaneous extrusion of strand shield, insulation and insulation shield combines to form a virtually perfect cable core eliminating unequal electrical stress
- XLP insulation offers low moisture absorption, good chemical resistance, low dielectric loss, and high dielectric strength
- Also offers tree retardant characteristics
Temperature Ratings:
- Normal: 90?C
- Emergency:130?C
- Short Circuit: 250?C
Standards:
- XLP insulation offers low moisture absorption, good chemical resistance, low dielectric loss, and high dielectric strength
- Also offers tree retardant characteristics
Temperature Ratings:
- Normal: 90?C
- Emergency:130?C
- Short Circuit: 250?C
- AEIC CS5; ICEA S-66-524/NEMA WC-7; RUS
- Conductor:ASTM B-231 and ICEA S-66-524/NEMA WC7
- Insulation: ICEA S-66-524/NEMA WC7 and AEIC CS5
- Concentric Conductor is 14, 12, 10, 9 AWG solid annealed copper meeting ASTM B-3
- Conductor:ASTM B-231 and ICEA S-66-524/NEMA WC7
- Insulation: ICEA S-66-524/NEMA WC7 and AEIC CS5
- Concentric Conductor is 14, 12, 10, 9 AWG solid annealed copper meeting ASTM B-3
Part # | AWG | No. of Strands | Nominal Insulation Thickness | Neutral AWG | Diameter Over Insulation | Nominal O.D. | Lbs./M’ |
1MVX30201A | 2 | 7 | .220” | 10×14 | .770” | 1.11” | 455 |
1MVX30101A | 1 | 19 | .220” | 13×14 | .810” | 1.16” | 523 |
1MVX31/001A | 1/0 | 19 | .220” | 16×14 | .850” | 1.20” | 598 |
1MVX32/001A | 2/0 | 19 | .220” | 13X12 | .905” | 1.28” | 701 |
1MVX33/001A | 3/0 | 19 | .220” | 16×12 | .955” | 1.33” | 813 |
1MVX34/001A | 4/0 | 19 | .220” | 13X10 | 1.00” | 1.43” | 971 |