CONSTRUCTION | |||||||||||||
Conductor: | - Stranded soft drawn tinned copper, Class B | ||||||||||||
Insulation: | - Flame retardant ethylene propylene rubber meeting the requirements for EPR VW-1 per UL | ||||||||||||
Assembly: | - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary - A binder tape (when required) of synthetic material assembles the core in a tight circular configuration |
||||||||||||
Color Code Chart 106: |
|
||||||||||||
Jacket: | - Black sunlight resistant thermoplastic Chlorinated Polyethylene (CPE) |
Applications:
Standards:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
- UL Type TC 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-95-658 / NEMA WC70
- ICEA-T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
Part # | AWG Size | No. of Cond. | Nom. Insul. Thick. | Nom. Jacket Thick. | Nom. O.D. | Lbs./M | Chart Reference | Recommended Fitting |
1AF161002* | 10 | 2 | .030” | .045” | .275” x .460” | 130 | Chart 106 | |
1AF161003 | 10 | 3 | .030” | .045” | .480” | 160 | Chart 106 | TCF05054A |
1AF161004 | 10 | 4 | .030” | .060” | .560” | 220 | Chart 106 | TCF05067A |
1AF161005 | 10 | 5 | .030” | .060” | .615” | 284 | Chart 106 | TCF05067A |
1AF161007 | 10 | 7 | .030” | .060” | .670” | 381 | Chart 106 | TCF05067A |
1AF161009 | 10 | 9 | .030” | .060” | .785” | 488 | Chart 106 | TCF07588A |
1AF161012 | 10 | 12 | .030” | .080” | .950” | 651 | Chart 106 | TCF100100A |
*ER Rating only applies to 3 conductors or more