TRAY CABLE, FREP®* - XHHW-2 - (VW-1)
FR-EP Insulation - CPE Jacket
90°C - 600 Volt - UL Type TC
ER Rated


CONSTRUCTION
Conductor: - Stranded soft drawn tinned copper, Class B
Insulation: - Flame retardant ethylene propylene rubber meeting the requirements for EPR VW-1 per UL
Assembly: - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary
- A binder tape (when required) of synthetic material assembles the core in a tight circular configuration
Color Code Chart 107:
Cond. Num. Color Cond. Num. Color
1 Black 2 Red
3 Blue 4 Orange
5 Yellow 6 Brown
7 Red w/ Black Stripe 8 Blue w/ Black Stripe
9 Orange w/ Black Stripe 10 Yellow w/ Black Stripe
11 Brown w/ Black Stripe 12 Black w/ Red Stripe
13 Blue w/ Red Stripe 14 Orange w/ Red Stripe
15 Yellow w/ Red Stripe 16 Brown w/ Red Stripe
17 Black w/ Blue Stripe 18 Red w/ Blue Stripe
19 Orange w/ Blue Stripe 20 Yellow w/ Blue Stripe
21 Brown w/ Blue Stripe 22 Black w/ Orange Stripe
23 Red w/ Orange Stripe 24 Blue w/ Orange Stripe
25 Yellow w/ Orange Stripe 26 Brown w/ Orange Stripe
27 Black w/ Yellow Stripe 28 Red w/ Yellow Stripe
29 Blue w/ Yellow Stripe 30 Orange w/ Yellow Stripe
31 Brown w/ Yellow Stripe 32 Black w/ Brown Stripe
33 Red w/ Brown Stripe 34 Blue w/ Brown Stripe
35 Orange w/ Brown Stripe 36 Yellow w/ Brown Stripe
37 Black
Jacket: - Black sunlight resistant thermoplastic Chlorinated Polyethylene (CPE)
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
Standards:
- UL Type TC 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-95-658 / NEMA WC70
- ICEA-T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
Part # AWG Size No. of Cond. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
1AF11402F* 14 2 Flat .045” .365” x .230” 61 -
1AF11402* 14 2 .045” .370” 71 TCF05040A
1AF11403 14 3 .045” .390” 92 TCF05040A
1AF11404 14 4 .045” .425” 115 TCF05040A
1AF11405 14 5 .045” .465” 139 TCF05054A
1AF11407 14 7 .045” .505” 183 TCF05054A
1AF11409 14 9 .060” .620” 250 TCF05067A
1AF11412 14 12 .060” .700” 317 TCF05078A
1AF11415 14 15 .080” .758” 393 TCF05078A
1AF11419 14 19 .060” .815” 468 TCF07588A
1AF11425 14 25 .080” .985” 645 TCF100100A
1AF11430 14 30 .080” 1.05” 747 TCF125109A
1AF11437 14 37 .080” 1.13” 897 TCF125128A
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.
*ER Rating only applies to 3 conductors or more