CONSTRUCTION | |||||||||||||
Conductor: | - Bare, annealed copper per ASTM B3 - Class B stranding per ASTM B8 |
||||||||||||
Color Code Chart 108: |
|
||||||||||||
Insulation: | - PVC/Nylon | ||||||||||||
Shield: | - 5 mils copper tape, 100% coverage - Helically applied w/ 25% overlap |
||||||||||||
Ground Wire: | - 6 AWG, 7 strand bare copper, uninsulated | ||||||||||||
Jacket: | - PVC, flame retardant, moisture, and sunlight resistant |
Standards:
- UL Type TC, 600 Volt
- NEC Type THHN/THWN Conductors
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- ICEA T-29-520 (210,000 BTU/hr.)
- IEEE 383 (70,000 BTU/hr.)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
Features:
- NEC Type THHN/THWN Conductors
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- ICEA T-29-520 (210,000 BTU/hr.)
- IEEE 383 (70,000 BTU/hr.)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
- Oil and chemical resistance
- Sunlight, cold bend, and cold impact resistance
- Rated at 90°C dry, 75°C wet
Applications:
- Sunlight, cold bend, and cold impact resistance
- Rated at 90°C dry, 75°C wet
- In all raceways, or direct burial
- In wet or dry locations
- Permitted for use in Class I Division 2 industrial hazardous locations per NEC Article 501-4b for UL Type TC cables
- In wet or dry locations
- Permitted for use in Class I Division 2 industrial hazardous locations per NEC Article 501-4b for UL Type TC cables
Part # | AWG Size | No. of Cond. | Grd. Size | Nom. Insul. Thick. | Nom. Jacket Thick | Nom. O.D. | Lbs./M’ | Recommended Fitting |
1A40803 | 8 | 3 | 10 | .036” | .060” | .620” | 342 | TCF07567A |
1A40603 | 6 | 3 | 8 | .036” | .060” | .705” | 474 | TCF10078A |
1A40403 | 4 | 3 | 6 | .048” | .080” | .895” | 710 | TCF100100A |
1A40203 | 2 | 3 | 6 | .048” | .080” | 1.02” | 1039 | TCF100109A |
1A40804 | 8 | 4 | 10 | .036” | .060” | .670” | 415 | TCF07578A |
1A40604 | 6 | 4 | 8 | .036” | .060” | .765” | 585 | TCF07578A |
1A40404 | 4 | 4 | 6 | .048” | .080” | .985” | 840 | TCF100100A |
1A40204 | 2 | 4 | 6 | .048” | .080” | 1.12” | 1168 |