CONSTRUCTION | |||||||||||||
Conductor: | - Bare annealed copper conforming to ASTM B3 and Class B stranded in accordance to ASTM B8 | ||||||||||||
Insulation: | - PVC/Nylon Type TFN in accordance with UL 62, flame retardant, 90°C temperature rating | ||||||||||||
Shield: | - Aluminum foil/polyester shield with 100% coverage | ||||||||||||
Color Code Chart 106: |
|
||||||||||||
Jacket: | - UL listed sunlight and moisture resistant, sequentially length marked, black, flame retardant polyvinyl chloride material - Nylon ripcord is included for ease of jacket removal |
||||||||||||
Drain Wire: | - 7 Strand Tinned Copper |
Applications:
- For use in cable trays, raceways, conduit or for aerial applications where installed with a messenger
- For use within Class 1 Division 2 and Class 2 Division 2 Hazardous Locations and Intrinsically Safe applications
- May be used in Class 1 Circuits
- May be used as permitted for nonpower-limited fire alarm circuits
Standards:
- For use within Class 1 Division 2 and Class 2 Division 2 Hazardous Locations and Intrinsically Safe applications
- May be used in Class 1 Circuits
- May be used as permitted for nonpower-limited fire alarm circuits
- UL Type TC, 600 Volt
- UL 1685
- IEEE 383
- UL 1277
- NEC 336.10
- NEC 760.27
- Meets -40?C cold bend test
- UL 1685
- IEEE 383
- UL 1277
- NEC 336.10
- NEC 760.27
- Meets -40?C cold bend test
Part # | AWG Size | No. of Conductors | Nom. Jacket Thick. | Nom. O.D. | Lbs./M’ | Chart Reference | Recommended Fitting |
1A171402* | 14 | 2 | .045” | .328” | 67 | Chart 106 | TCF07540A |
1A171602* | 16 | 2 | .045” | .300” | 52 | Chart 106 | TCF07540A |
1A171603 | 16 | 3 | .045” | .320” | 63 | Chart 106 | TCF07540A |
1A171802 | 18 | 2 | .045” | .280” | 40 | Chart 106 | TCF07540A |
1A171803 | 18 | 3 | .045” | .290” | 49 | Chart 106 | TCF07540A |
*ER Rating only applies to 3 conductors or more