Variable Frequency Drive TC-ER, XLP/PVC
Low Voltage Power - 2000V
90°C Wet or Dry


CONSTRUCTION
Conductor: - Annealed bare stranded copper
Insulation: - XLP/PVC
Shield: - Bare Copper Tape Shield with a 50% overlap
Jacket: - Flame-retardant, moisture and sunlight resistant PVC
Specifications:
- UL Type TC-ER
- UL 1277 Type TC-ER, 2000V
- UL Type RHH or RHW-2 conductors per UL 44
- IEEE 383
- IEEE 1202
- EPA 40 CFR, Part 261 for leachable lead content per TCLP
- OSHA acceptable
Applications:
- For use with AC motors controlled by Pulse Width Modulated Inverter in VFD applications rated up to 2000 volts
- In raceways, cable trays or direct burial
- In wet or dry locations
- Permitted for use in Class 1, Division 2 industrial hazardous locations per NEC
- Permitted for Exposed Run or ER use in accordance with NEC
Part # AWG Size No. of Cond. Ground Wire AWG Nom. Insulation Thick. Nom. Jacket Thick. Nom. O.D. Lbs./M’
1AV11403 14 3 3X18 0.060” 0.060” 0.580” 212
1AV11203 12 3 3X16 0.060” 0.060” 0.615” 260
1AV11003 10 3 3X14 0.060” 0.060” 0.670” 329
1AV10803 8 3 3X14 0.070” 0.060” 0.770” 441
1AV10603 6 3 3X12 0.070” 0.080” 0.895” 618
1AV10403 4 3 3X12 0.070” 0.080” 0.995” 830
1AV10203 2 3 3X10 0.070” 0.080” 1.125” 1152
1AV11/003 1/0 3 3X6 0.090” 0.080” 1.385” 1853
1AV12/003 2/0 3 3X6 0.090” 0.080” 1.480” 2169
1AV13/003 3/0 3 3X5 0.090” 0.080” 1.590” 2619
1AV14/003 4/0 3 3X4 0.090” 0.110” 1.780” 3241
1AV125003 250 3 3X4 0.105” 0.110” 1.940” 3763
1AV135003 350 3 3X2 0.105” 0.110” 2.160” 5109
1AV150003 500 3 3X1 0.105” 0.110” 2.455” 6933
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.