CONSTRUCTION | |
Conductor: | - Flexible stranded 27% nickel plated, annealed copper |
Insulation: | - Mica/glass tapes |
Braid: | - Glass braid applied over the mica |
Jacket: | - Red fiberglass braid jacket |
Applications:
- Used in critical areas where standard high temperature lead wire is not sufficient to maintain circuit integrity due to extreme temperatures, or exposure to open flame
- Used for equipment wiring in iron mills, steel mills, glass plants, and cement kilns
Standards:
- Used for equipment wiring in iron mills, steel mills, glass plants, and cement kilns
- UL approved lead wire 450°C
- IEEE 383 modified 210,000 BTU vertical tray flame test at 1800°F, with circuit integrity for 2.5 hours minimum
- Non-UL operating temperature can withstand up to 2400°F short term.
- IEEE 383 modified 210,000 BTU vertical tray flame test at 1800°F, with circuit integrity for 2.5 hours minimum
- Non-UL operating temperature can withstand up to 2400°F short term.
Part # | AWG Size | No. of Cond. | Stranding | Nom. Insul.Thick. | Nom. Jacket Thick. | Nom. O.D. | Lbs./M’ | Amps |
1C31803 | 18 | 3 | 16 | .025” | .007” | .327” | 55 | 31 |
1C31804 | 18 | 4 | 16 | .025” | .007” | .345” | 69 | 31 |
1C31403 | 14 | 3 | 41 | .025” | .017” | .390” | 93 | 55 |
1C31405 | 14 | 5 | 41 | .025” | .017” | .469” | 147 | 55 |
1C31202 | 12 | 2 | 65 | .025” | .017” | .400” | 87 | 75 |
1C31203 | 12 | 3 | 65 | .025” | .017” | .426” | 120 | 75 |
* Ampacity based on single conductor in free air at an ambient air temperature of 40°C (107°C)