ARMORED CABLE, Aluminum Interlocked Armor
EPR Insulation - Non-Shielded
90°C - 2.4kV - UL Type MV-90


CONSTRUCTION
Conductor: - Bare copper, compact Class B strand
Extruded Strand Shield: - Extruded thermoset semi-conducting stress control layer over conductor
Insulation: - Ethylene propylene rubber colored to contrast with black conducting shield layer
Ground: - Annealed bare copper Class B stranding per ASTM B8
Armor: - Aluminum Interlocker Armor
Jacket: - Flame-retardant, moisture, and sunlight resistant polyvinyl chloride (PVC)
Applications:
- Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is the major concern, maximum performance will be demanded, space is limited, and fire resistance is necessary
- May be installed in wet or dry locations, indoors or outdoors and in exposed or concealed work
- May be used in cable trays or on approved supports in protected areas
Standards:
- ICEA S-96-659
- NEMA WC-71
- UL 1072
- UL 1569
- IEEE 1202
- IEEE 383
- UL 1581
- ICEA T-29-520
- ICEA T-30-520
- EPA 40 CFR part 261
- OSHA Acceptable
Part # No. of Cond. Cond. Size Cond. Diam. Ground Size Insul. Thick. Diam. Over Armor Nom. Jacket Thick. Nom. O.D. Lbs./M’
1Y70603A 3 6 .170” 6 .115” 1.16” .050” 1.27” 854
1Y70403A 3 4 .210” 6 .115” 1.26” .050” 1.37” 1056
1Y70203A 3 2 .270” 6 .115” 1.37” .050” 1.48” 1363
1Y71/003A 3 1/0 .340” 4 .115” 1.61” .060” 1.74” 2003
1Y72/003A 3 2/0 .380” 4 .115” 1.71” .060” 1.84” 2326
1Y74/003A 3 4/0 .480” 3 .115” 1.92” .060” 2.05” 3256
1Y725003A 3 250 .520” 3 .115” 2.00” .060” 2.13” 3689
1Y735003A 3 350 .620” 2 .115” 2.21” .060” 2.34” 4825
1Y750003A 3 500 .740” 1 .115” 2.46” .075” 2.63” 6567
1Y775003A 3 750 .910” 1/0 .115” 2.83” .075” 3.00” 9320
Note: The data shown are approximate and subect to standard industry and manufacturer tolerances.