ARMORED CABLE, Aluminum Interlocked Armor
EPR Insulation - Shielded
105°C - 5kV - UL Type MV-105


CONSTRUCTION
Conductor: - Stranded, bare copper in accordance with ASTM B3 and B8
Insulation: - EPR (ethylene propylene rubber) with average thickness of .075" meeting the requirements of the referenced standards
Grounding Conductor: - Stranded bare copper in accordance with ASTM B3 and B8
Assembly: - The insulated power conductors will be cabled round with fillers and with a grounding conductor in one outer interstice and covered with a binder tape
Armor: - Aluminum interlocked armor
Jacket: - Flame and sunlight resistant Yellow PVC jacket
Conductor Shield: - Extruded semi-conducting thermosetting polymeric layer firmly bonded to the insulation
Applications:
- Designed for use on power or control circuits
- Can be installed in cable tray (NEC Article 318), wire ways, racks, or buried directly
Standards:
- UL 1072
- Flame Rated: IEEE-1202 (70,000 BTU)
- UL Type MV-105
- ICEA Pub. No. S-68-516 & NEMA Pub. No. WC8
Part # AWG Size No. of Cond. Ground No. x AWG Nom. O.D. Lbs./M’ Ampacity* / +
Armor Overall
1Y20203A 2 3 1 x #6 1.51” 1.77” 1819 200/160
1Y21/003A 1/0 3 1 x #4 1.60” 1.92” 2364 230/185
1Y22/003A 2/0 3 1 x #4 1.69” 2.00” 2696 260/215
1Y24/003A 4/0 3 1 x #3 2.09” 2.22” 3687 335/285
1Y225003A 250 3 1 x #3 2.21” 2.34” 4165 365/320
1Y235003A 350 3 1 x #2 2.41” 2.57” 5436 440/395
1Y250003A 500 3 1 x #1 2.64” 2.84” 7170 530/485
1Y275003A 750 3 1 x #1/0 3.00” 3.14” 10084 650/615
Note: The data shown are approximate and subect to standard industry and manufacturer tolerances.
*Direct burial ampacities are based on Table 310-83 three conductors within an overall covering directly buried, 90°C conductor, 20°C earth ambient temperature.
+ In air ampacities are based on 310-71 three conductors within an overall covering in free air, 90°C conductor, 40°C ambient temperature.