ARMORED CABLE, Aluminum Interlocked Armor
90°C - 600 Volt
UL Type MC


CONSTRUCTION
Conductor: - Stranded, bare copper in accordance with ASTM B3 and B8
Insulation: - Cross-linked polyethylene type XHHW-2 per UL44
Grounding Conductor: - Class B stranded bare copper in accordance with ASTM B3 and B8
Assembly: - Conductors are cabled with suitable fillers and bare copper ground conductor
- Cable core is covered with binder tape
Armor: - Aluminum interlocked armor
Color Code Chart 107 (Y11204A & Y11004A):
Cond. Num. Color Cond. Num. Color
1 Black 2 Red
3 Blue 4 Orange
5 Yellow 6 Brown
7 Red w/ Black Stripe 8 Blue w/ Black Stripe
9 Orange w/ Black Stripe 10 Yellow w/ Black Stripe
11 Brown w/ Black Stripe 12 Black w/ Red Stripe
Color Code Chart 108 (Y10604A & Y10204A):
Cond. Num. Cond. Marking Cond. Num. Cond. Marking
1 "1" One 2 "2" Two
3 "3" Three 4 "4" Four
Jacket: - Flame and sunlight resistant black PVC jacket
Standards:
- UL 1569, UL 44, UL 1581, UL Type MC-600 volts
- ICEA S-95-658/NEMA WC 70, ICEA T-29-520
- NEC Type XHHW-2 conductors
- IEEE 383, IEEE 1202
- Meets EPA 40 CFR part 261
- OSHA acceptable, NEC
Applications:
- Designed for use on power or control circuits
- Can be installed in cable tray, wire ways, racks, or buried directly
- Permitted for use in Class I, Division II and Class II, Division II per NEC
Part # AWG Size No. of Cond. Nom. Insul. Thick. Nom. Jacket Thick. Ground AWG Size Nom. O.D. Lbs./M’ Ampacity* 40°C Ambient Recommended Fitting
Armor Overall
1Y11204A 12 4 .030” .050” 12 .58” .69” 295 - STE050
1Y11004A 10 4 .030” .050” 10 .68” .79” 345 - STE050
1Y10804A 8 4 .045” .050” 10 .81” .91” 501 44   STE075
1Y10604A 6 4 .045” .050” 8 .91” 1.01” 686 60 STE075
1Y10404A 4 4 .045” .050” 8 1.01” 1.11” 927 88 STE100
1Y10204A 2 4 .045” .050” 6 1.15” 1.25” 1333 104 STE125
1Y10104A 1 4 .055” .050” 6 1.37” 1.47” 1670 120 STE125
1Y11/004A 1/0 4 .055” .050” 6 1.47” 1.57” 1990 136 STE150
1Y12/004A 2/0 4 .055” .060” 6 1.57” 1.69” 2416 156 STE150
1Y13/004A 3/0 4 .055” .060” 4 1.69” 1.81” 3313 180 STE200
1Y14/004A 4/0 4 .055” .060” 4 1.83” 1.95” 3590 208 STE200
1Y125004A 250 4 .065” .060” 4 1.99” 2.11” 4320 232 STE200
1Y135004A 350 4 .065” .075” 3 2.25” 2.40” 5914 280 STE250
1Y150004A 500 4 .065” .075” 2 2.57” 2.72” 8038 344 STE250
1Y175004A 750 4 .080” .085” N/A 3.09” 3.26” 11825 428 STE300
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.
*Ampacity per NEC Table 310-16