ARMORED CABLE, Aluminum Interlocked Armor
Individual and Overall Shield
90°C - 600 Volt


CONSTRUCTION
Conductor: - Bare copper, per ASTM Class B
Insulation: - Cross-linked Polyethylene (XLPE)
- Color Code: M1, E1
Assembly: - Pair or triad twisted with a drain wire and Aluminum/Mylar shield overall
- Pairs are cabled together with a drain wire and Aluminum/Mylar shield overall
Inner Jacket: - Black Polyvinylchloride (PVC)
Armor: - Interlocked Aluminum armor
Outer Jacket: - Black Polyvinylchloride (PVC)
Color Code (Pairs):
Cond. Num. Color
1 Black, White - ONE
2 Black, White - TWO
3 Black, White - THREE
4 Black, White - FOUR
Standards:
- UL listed as Type MC, per UL Standard 1569 for metal clad cables
- Meets UL 1581, 1202, & ICEA T-29-520
- RoHS Compliant
Applications:
- UL approved for Direct Burial
- Sunlight and Oil Resistant
- Rated for CT use
- Suitable for use in Class I Division II hazardous locations
Part # AWG Size Pairs Outer Jacket Thick. O.D. Over Armor Nom. O.D. Lbs./M’ Recommended Fitting for Standard Locations Recommended Fitting for Hazardous Locations
1T61602P 16(7) AWG 2 Pair .045” .693” .793” 300 STE050 STEX075
1T61604P 16(7) AWG 4 Pair .060” .866” .966” 510 STE075 STEX075
1T61606P 16(7) AWG 6 Pair .060” 1.011” 1.111” 690 STE075 STEX100
1T61608P 16(7) AWG 8 Pair .060” 1.028” 1.128” 770 STE075 STEX100
1T61612P 16(7) AWG 12 Pair .080” 1.241” 1.341” 1038 STE100 STEX125
1T61624P 16(7) AWG 24 Pair .080” 1.577” 1.697” 1798 STE150 STEX200
1T61802P 18(7) AWG 2 Pair .060” .663” .763” 267 STE050 STX050464
1T61804P 18(7) AWG 4 Pair .060” .803” .903” 438 STE050 STEX075
Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager.