CONSTRUCTION | |
Conductor: | - Bare annealed copper per ASTM B3 - Compact stranding per ASTM B496 |
Extruded Strand Shield: | - Extruded thermoset semi-conductor stress control layer over conductor per ICEA S-93-639 and UL 1072 |
Insulation: | - 220 mils EPR per ICEA S-93-639 and UL 1072 |
Extruded Insulation Shield: | - Thermoset semi-conducting polymeric layer, free stripping from the insulation per ICEA S-93-639 and UL 1072 |
Shield: | - 5 mil annealed bare copper tape with 25% overlap - Color coded polymeric identification tape laid under the shield: Black, Red, & Blue |
Grounding Conductor: | - Class B stranded bare annealed copper grounding conductor - Sized in accordance with UL 1072 and NEC Article 250 |
Cable Assembly: | - Insulated and grounding conductors are cabled together with non-hygroscopic fillers when required - Binder tape is applied over the cabled core |
Armor: | - Impervious, continuously welded and corrugated aluminum alloy sheath |
Jacket: | - Flame-retardant, moisture and sunlight resistant PVC, red - Low temperature performance meets ASTM D746 brittleness temperature at or below 40°C |
Features:
- Cable meets cold impact at -40°C
- 105°C continuous operating temperature, wet or dry
- 140°C emergency rating
- 250°C short circuit rating
Applications:
- 105°C continuous operating temperature, wet or dry
- 140°C emergency rating
- 250°C short circuit rating
- For use in feeders and branch circuits in industrial power distribution systems per NEC articles 328 and 330
- Approved for Classes I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2, hazardous locations covered under NEC Articles 501, 502, and 503.
- Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced no more than 6 feet apart
- Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete
- Approved for Classes I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2, hazardous locations covered under NEC Articles 501, 502, and 503.
- Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced no more than 6 feet apart
- Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete
Part # | AWG Size | No. of Cond. | Grd. Size | Nom. Insul. Thick. | Nom. O.D. | Lbs./M’ | |
Armor | Overall | ||||||
1XMVE30203 | 2 | 3 | 6 | .220” | 2.15” | 2.28” | 2473 |
1XMVE31/003 | 1/0 | 3 | 4 | .220” | 2.32” | 2.48” | 3190 |
1XMVE32/003 | 2/0 | 3 | 4 | .220” | 2.40” | 2.56” | 3630 |
1XMVE34/003 | 4/0 | 3 | 3 | .220” | 2.62” | 2.79” | 4435 |
1XMVE325003 | 250 | 3 | 3 | .220” | 2.75” | 2.92” | 5086 |
1XMVE335003 | 350 | 3 | 2 | .220” | 3.03” | 3.21” | 6445 |
1XMVE350003 | 500 | 3 | 1 | .220” | 3.32” | 3.50” | 8376 |
1XMVE375003 | 750 | 3 | 1/0 | .220” | 3.80” | 3.98” | 11431 |