CONSTRUCTION | |
Conductor: | - Bare annealed copper per ASTM B3 - Compact stranding per ASTM B496 |
Extruded Strand Shield: | - Extruded thermoset semi-conductor stress control layer over conductor per ICEA S-96-659 and UL 1072 |
Insulation: | - 90 mils EPR per ICEA S-96-659 and UL 1072 - Insulation is printed 1-Black, 2-Red, and 3-Blue for phase identification |
Grounding Conductor: | - Three split Class B stranded bare annealed copper grounding conductors - Sized in accordance with UL 1072 and NEC Table 250.122 |
Armor: | - Continuous, impervious, welded, corrugated aluminum armor |
Jacket: | - Flame-retardant, moisture and sunlight resistant PVC, yellow - Low temperature performance meets ASTM D746 brittleness temperature at or below 40°C |
Applications:
- Variable Frequency Drives: 3-conductor CCW armored cables with 3 symmetrical grounding wire are the preferred wiring method for use with AC motors controlled by pulse-width modulated inverters in VFD applications
- For use in feeders and branch circuits in industrial power distribution systems per NEC articles 328 and 330
- Approved for Classes I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2, hazardous locations covered under NEC Articles 501, 502, and 503.
- Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced no more than 6 feet apart
- Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete
Features:
- For use in feeders and branch circuits in industrial power distribution systems per NEC articles 328 and 330
- Approved for Classes I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2, hazardous locations covered under NEC Articles 501, 502, and 503.
- Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced no more than 6 feet apart
- Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete
- Cable meets cold impact at -40°C
- 90°C continuous operating temperature, wet or dry
- 140°C emergency rating
- 250°C short circuit rating
- 90°C continuous operating temperature, wet or dry
- 140°C emergency rating
- 250°C short circuit rating
Part # | AWG Size | No. of Cond. | Grd. Size | Nom. Insul. Thick. | Nom. O.D. | Lbs./M’ | |
Armor | Overall | ||||||
1XMVE10403 | 4 | 3 | 3 x #10 | .090” | 1.19” | 1.30” | 965 |
1XMVE10203 | 2 | 3 | 3 x #10 | .090” | 1.34” | 1.45” | 1275 |
1XMVE11/003 | 1/0 | 3 | 3 x #8 | .090” | 1.51” | 1.65” | 1840 |
1XMVE12/003 | 2/0 | 3 | 3 x #8 | .090” | 1.60” | 1.73” | 2165 |
1XMVE14/003 | 4/0 | 3 | 3 x #7 | .090” | 1.83” | 1.96” | 3080 |
1XMVE125003 | 250 | 3 | 3 x #7 | .090” | 1.96” | 2.09” | 3475 |
1XMVE135003 | 350 | 3 | 3 x #6 | .090” | 2.19” | 2.32” | 4710 |
1XMVE150003 | 500 | 3 | 3 x #5 | .090” | 2.45” | 2.61” | 6410 |
1XMVE175003 | 750 | 3 | 3 x #4 | .090” | 2.93” | 3.10” | 9225 |