CONSTRUCTION | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Conductor | - Bare, annealed copper conforming to ASTM B-3 and stranded in accordance with ASTM B8. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Insulation: | - Cross-linked polyethylene type XHHW per UL 44. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Color Code for 6AWG and smaller: |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Color Code for 4AWG and larger: | - Black with printed numbers per ICEA Method 4 |
Applications:
- For use as services, feeders and branch circuits for power, lighting, control, and signal circuits in accordance with NEC articles 330 and 725
- Class I, II and III, Divisions 1 and 2; Class I, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503, and 505.
- Installed indoors or outdoors, wet or dry locations, directly buried, embedded in concrete, in a raceway, as aerial on a messenger, or as exposed runs secured to supports in accordance with NEC article 330
Features:
- Class I, II and III, Divisions 1 and 2; Class I, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503, and 505.
- Installed indoors or outdoors, wet or dry locations, directly buried, embedded in concrete, in a raceway, as aerial on a messenger, or as exposed runs secured to supports in accordance with NEC article 330
- CCW armor provides an impervious barrier to moisture, gas and liquids
- CCW armor provides EMI shielding performance
- Meets cold impact at -40°C
- Factory assembled and tested cable for use as an alternate to cable in conduit wiring systems
- 90°C continuous operating temperature, wet or dry
- 130°C emergency rating
- 250°C short circuit rating
- CCW armor provides EMI shielding performance
- Meets cold impact at -40°C
- Factory assembled and tested cable for use as an alternate to cable in conduit wiring systems
- 90°C continuous operating temperature, wet or dry
- 130°C emergency rating
- 250°C short circuit rating
Part # | AWG Size | No. of Cond. | Ground Size | Nom. O.D. | Lbs./M’ | |
Armor | Overall | |||||
1XA60804 | 8 | 4 | 10 | .800” | .900” | 473 |
1XA60604 | 6 | 4 | 8 | .890” | .990” | 641 |
1XA60404 | 4 | 4 | 8 | .970” | 1.08” | 860 |
1XA60204 | 2 | 4 | 6 | 1.15” | .1.26” | 1267 |
1XA62/004 | 2/0 | 4 | 6 | 1.51” | .1.64” | 2351 |
1XA64/004 | 4/0 | 4 | 4 | 1.78” | .1.91” | 3491 |
1XA635004 | 350 | 4 | 3 | 2.19” | .2.35” | 5536 |
1A650004 | 500 | 4 | 2 | 2.49” | .2.65” | 7704 |