CONSTRUCTION | |||||||||||||
Conductor: | - Bare, annealed copper conforming to ASTM B-3 - 10AWG and smaller are Class B compressed stranding per ASTM B8 - 8AWG and larger are compact stranding per ASTM B496 |
||||||||||||
Insulation: | - Cross-linked polyethylene type XHHW per UL 44, listed XHHW-2 | ||||||||||||
Grounding Conductor: | - Class B stranded bare annealed copper per ASTM B3 and B8 | ||||||||||||
CCW Armor: | - Impervious, continuously welded and corrugated aluminum alloy sheath | ||||||||||||
Jacket: | Flame retardant, moisture and sunlight resistant PVC, black | ||||||||||||
Color Code for Power Conductors, 6AWG and smaller: |
|
||||||||||||
Color Code for Power Conductors, 4AWG and larger: | - Black with printed numbers per ICEA Method 4 |
Applications:
- For use as services, feeders and branch circuits for power, lighting, control, and signal circuits in accordance with NEC articles 330 and 725
- Class I, II and III, Divisions 1 and 2; Class I, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503, and 505.
- Installed indoors or outdoors, wet or dry locations, directly buried, embedded in concrete, in a raceway, as aerial on a messenger, or as exposed runs secured to supports in accordance with NEC article 330
- Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute
Features:
- Class I, II and III, Divisions 1 and 2; Class I, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503, and 505.
- Installed indoors or outdoors, wet or dry locations, directly buried, embedded in concrete, in a raceway, as aerial on a messenger, or as exposed runs secured to supports in accordance with NEC article 330
- Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute
- CCW armor provides an impervious barrier to moisture, gas and liquids
- CCW armor provides EMI shielding performance
- Meets cold impact at -40°C
- Factory assembled and tested cable for use as an alternate to cable in conduit wiring systems
- 90°C continuous operating temperature, wet or dry
- 130°C emergency rating
- 250°C short circuit rating
- CCW armor provides EMI shielding performance
- Meets cold impact at -40°C
- Factory assembled and tested cable for use as an alternate to cable in conduit wiring systems
- 90°C continuous operating temperature, wet or dry
- 130°C emergency rating
- 250°C short circuit rating
Part # | Power Conductor Size | Control Conductor Size | Bare Ground AWG | Nom. O.D. | Lbs./M’ | Recommended Fittings for Standard Locations | Recommended Fittings for Hazardous Locations | |
Armor | Overall | |||||||
1XAC31003 | 3 × 10AWG | 4 x #12AWG | 10 | .750” | .860” | 430 | STE050 | STEX075 |
1XAC30803 | 3 × 8AWG | 4 x #12AWG | 10 | .890” | .990” | 535 | STE050 | STEX075 |
1XAC30603 | 3 × 6AWG | 4 x #12AWG | 8 | .930” | 1.03” | 660 | STE075 | STEX100 |
1XAC30403 | 3 × 4AWG | 4 x #12AWG | 8 | .970” | 1.08” | 815 | STE075 | STEX100 |