CONSTRUCTION | |
Conductor: | - Bare, annealed copper conforming to ASTM B-3 and stranded in accordance with ASTM B8 (Class B) |
Insulation: | - Flame-retardant PVC insulation and nylon covering, rated 105°C per UL Standard 13 & 2250 - Color Code: ICEA Method 1 |
Individual Shield: | - Aluminum/polyester tape with 100% coverage - Stranded tinned copper drain wire, two sizes small than conductors |
Overall Shield: | - Aluminum/polyester tape shield providing 100% coverage - Stranded tinned copper drain wire, same size as insulated conductors |
Inner Jacket: | - Flame-retardant PVC per UL Standards 13 and 2250 - Low temperature performance meets ASTM D746 brittleness temperature at or below 40°C - Nylon rip cord to facilitate jacket removal |
Armor: | - Impervious, continuously corrugated and welded aluminum per UL 1569 - Meets grounding requirements of NEC Article 250 |
Overall Jacket: | - Flame-retardant, moisture and sunlight resistant PVC per UL Standards 13 and 2250 - Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C - Nylon ripcord |
Applications:
- For use as Power Limited Tray Cable on circuits rated 150V or less and 5 amps or less in Class 2 or Class 3 circuits in accordance with NEC Article 725
- For use as instrumentation tray cable on circuits rated 150V or less and 5 amps or less in accordance with NEC article 727
- Recognized for use in Class I, II, and III, Divisions 1 and 2; or Class 1, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503 and 505.
- Installed indoors or outdoors, in wet or dry locations, in a raceway, as aerial cable on a messenger, in cable trays , or for direct burial
- Recognized for use on fixed or floating offshore petroleum facilities as recommended by American Petroleum Institute.
Features:
- For use as instrumentation tray cable on circuits rated 150V or less and 5 amps or less in accordance with NEC article 727
- Recognized for use in Class I, II, and III, Divisions 1 and 2; or Class 1, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503 and 505.
- Installed indoors or outdoors, in wet or dry locations, in a raceway, as aerial cable on a messenger, in cable trays , or for direct burial
- Recognized for use on fixed or floating offshore petroleum facilities as recommended by American Petroleum Institute.
- CCW provides EMI shielding performance
- Meets cold impact at -40°C
- Meets cold impact at -40°C
Part # | AWG Size | No. of Pair / Triad | Nom. O.D. | Lbs./M’ | ||
Core | Armor | Overall | ||||
1XL31602 | 16 | 2 pairs | .440” | .670” | .780” | 260 |
1XL31604 | 16 | 4 pairs | .520” | .710” | .820” | 334 |
1XL61604 | 16 | 4 triads | .580” | .800” | .910” | 392 |
1XL31608 | 16 | 8 pairs | .690” | .930” | 1.04” | 515 |
1XL61608 | 16 | 8 triads | .790” | 1.02” | 1.13” | 621 |
1XL31612 | 16 | 12 pairs | .810” | 1.06” | 1.17” | 684 |
1XL61612 | 16 | 12 triads | .950” | 1.19” | 1.30” | 879 |
1XL31624 | 16 | 24 pairs | 1.10” | 1.37” | 1.48” | 1270 |