CONSTRUCTION | |||||||||||||
Conductor: | - Annealed bare copper - Class B stranding in accordance with ASTM B8 - In sizes 8 AWG to 1000 kcmil, the conductors may be compact stranded to reduce cable diameter and weight |
||||||||||||
Insulation: | - Cross linked polyethylene, rated CSA C22.2 No. 38 type RW90 | ||||||||||||
Assembly: | - Cabled in concentric layers with grounding wire, interstices are filled with suitable nonhygroscopic fillers, as required - A binder tape of synthetic material assembles the core in an essentially round configuration, as required |
||||||||||||
Inner Jacket: | - Black polyvinyl chloride jacket | ||||||||||||
Armor: | - Interlocking aluminum tape armor applied over inner jacket | ||||||||||||
Outer Jacket: | - Black polyvinyl chloride jacket | ||||||||||||
Color Code: |
|
Applications:
- Suitable for use in ventilated, non-ventilated and ladder cable trays, direct earth burial or raceways, and for exposed or concealed wiring in wet, damp or dry locations
- Suitable for use in wet or dry locations when installed in accordance with the NEC
- Suitable for use in all hazardous locations when used with certified HL cable glands
Standards:
- Suitable for use in wet or dry locations when installed in accordance with the NEC
- Suitable for use in all hazardous locations when used with certified HL cable glands
- Meets the requirements of CSA C22.2 No. 38 type RW90 for unshielded conductors and CSA C68.3-97 for shielded conductors
- Meets CSA C22.2 No. 131
- CSA listed as Type Teck
- Suitable for direct burial and use in cable tray
- CSA FT1 & FT4
- 90°C wet or dry, -40°C low temp
- Jacket is oil resistant
- Meets CSA C22.2 No. 131
- CSA listed as Type Teck
- Suitable for direct burial and use in cable tray
- CSA FT1 & FT4
- 90°C wet or dry, -40°C low temp
- Jacket is oil resistant
Part # | AWG Size | No. of Cond. | Nom. Insul. Thick. | Nom. O.D. | Lbs./M’ | Amps | Ground AWG | Recommended Fitting for Standard Locations | Recommended Fitting for Hazardous Locations | |
Armor | Overall | |||||||||
1kV | ||||||||||
1T30803 | 8 | 3 | 45 mils | .860” | .940” | 482 | 45 | 10 | STE050 | STEX075 |
1T30804 | 8 | 4 | 45 mils | .920” | 1.00” | 570 | 45 | 10 | STE075 | STEX100 |
1T30603 | 6 | 3 | 60 mils | 1.03” | 1.13” | 695 | 65 | 8 | STE075 | STEX100 |
1T30604 | 6 | 4 | 60 mils | 1.04” | 1.25” | 883 | 65 | 8 | STE100 | STEX125 |
1T30403 | 4 | 3 | 60 mils | 1.16” | 1.25” | 950 | 85 | 8 | STE100 | STEX125 |
1T30404 | 4 | 4 | 60 mils | 1.18” | 1.27” | 1161 | 85 | 8 | STE100 | STEX125 |
1T30203 | 2 | 3 | 60mils | 1.28” | 1.37” | 1300 | 120 | 6 | STE100 | STEX125 |
1T30204 | 2 | 4 | 60mils | 1.45” | 1.53” | 1568 | 120 | 6 | STE125 | STEX150 |
1T31/003 | 1/0 | 3 | 80 mils | 1.56” | 1.68” | 1871 | 155 | 6 | STE150 | STEX200 |
1T32/003 | 2/0 | 3 | 80 mils | 1.65” | 1.77” | 2177 | 185 | 6 | STE150 | STEX200 |
1T33/003 | 3/0 | 3 | 80 mils | 1.75” | 1.87” | 2619 | 210 | 4 | STE150 | STEX200 |
1T34/003 | 4/0 | 3 | 80 mils | 1.86” | 1.98” | 3176 | 235 | 4 | STE200 | STEX250 |
1T335003 | 350 | 3 | 90 mils | 2.26” | 2.40” | 4989 | 325 | 3 | STE250 | STEX300 |
1T350003 | 500 | 3 | 90 mils | 2.52” | 2.66” | 6706 | 395 | 3 | STE250 | STEX300 |