BUILDING WIRE - 600 VOLT, XLP/USE-2 or RHW-2 or RHH
90°C - 600 Volt


CONSTRUCTION
Conductor: - Bare annealed copper, Class B stranding
Insulation: - Moisture and flame retardant thermoset crosslinked Polyethylene
Color Code Chart 123:
Jacket Num. Color Jacket Num. Color
1 Black 2 White
3 Red 4 Green
5 Blue 6 Gray
7 Orange 8 Yellow
9 Purple 10 Brown
Applications:
- Recognized for use as general purpose wiring at maximum conductor temperature of 90°C in dry and wet locations
- For installation in air, conduit, or other recognized raceways in circuits not exceeding 600 volts
- Tray cable rated available upon request for 1/0 and larger
Standards:
- USE-2 meets the requirements of UL 854 and UL 44
- RHW-2 meets the requirements of UL 44
- NEC Article 310
- ICEA No. S-66-524
- Direct burial rated
Additional Information:
- Can be provided in twisted configurations up to 10 AWG
- Sunlight and/or oil resistant available upon request
Features:
- Conductor for reduced diameter
General purpose use in construction:
- Residential
- Commercial
- Institutional
- Industrial construction
Part # AWG Stranding Nominal Insulation Thickness Nominal O.D. Lbs./M’
1M614ST-XX 14 7 .045” .162” 22
1M612ST-XX 12 7 .045” .188” 30
1M610ST-XX 10 7 .045” .212” 45
1M608ST-XX 8 7 .060” .270” 73
1M606ST-XX 6 7 .060” .310” 107
1M604ST-XX 4 7 .060” .360” 161
1M602ST-XX 2 7 .060” .420” 244
1M601ST-XX 1 19 .080” .490” 325
1M61/0ST-XX 1/0 19 .080” .530” 399
1M62/0ST-XX 2/0 19 .080” .580” 491
1M63/0ST-XX 3/0 19 .080” .630” 585
1M64/0ST-XX 4/0 19 .080” .690” 751
1M6250ST-XX 250 37 .095” .770” 865
1M6300ST-XX 300 37 .095” .820” 1030
1M6350ST-XX 350 37 .095” .880” 1190
1M6400ST-XX 400 37 .095” .920” 1350
1M6500ST-XX 500 37 .110” 1.03” 1670
1M6600ST-XX 600 61 .110” 1.11” 2015
1M6750ST-XX 750 61 .110” 1.22” 2495
1M61000ST-XX 1000 61 .110” 1.35” 3290
Note: The data shown is approximate and subject to standard industry and manufacturer tolerances.
Insert the color number in the XX location.