CONSTRUCTION | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Conductor: | - Bare, soft annealed copper per ASTM B-3 - 14 AWG (19 strand) |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Insulation: | - Each conductor is concentrically insulated with a 15 mil wall of high dielectric flame retardant polymer with 5 mil wall of clear polymide (nylon) jacket extruded over primary insulation and conforming to UL requirements | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cabling: | - The applicable number of conductors are cabled together with fillers as necessary with a suitable layer - A clear mylar tape is helically applied over the core |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Color Code Chart 107: |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Overall Jacket: | - Gas/vapor-tight heavy duty, flame and oil resistant neoprene (black) per UL-1277 and ICEA S-73-532 part 4 |
Applications:
- To be installed in trays, raceways, troughs, channels, ducts, conduit, and by direct burial
- Recommended for wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required
- Designed for control, power, lighting, telemetering, signal, relay traffic control, wherever flexible, small diameter cable is required such as cranes, hoists, and some robotics applications
- Cables can be flexed at -40°C
Standards:
- Recommended for wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required
- Designed for control, power, lighting, telemetering, signal, relay traffic control, wherever flexible, small diameter cable is required such as cranes, hoists, and some robotics applications
- Cables can be flexed at -40°C
- OSHA acceptable
- Recognized for use in Class 1 or 2, Division 2 hazardous locations
- UL Type power and control tray cables and Articles 318, 340, 500, and 501 of the NEC
- Cables pass UL 1277 and IEEE 383 (70,000 BTU) flame tests
- Cables are rated 600 volts, 90°C dry and 75°C wet. UL file no. E60749
- Recognized for use in Class 1 or 2, Division 2 hazardous locations
- UL Type power and control tray cables and Articles 318, 340, 500, and 501 of the NEC
- Cables pass UL 1277 and IEEE 383 (70,000 BTU) flame tests
- Cables are rated 600 volts, 90°C dry and 75°C wet. UL file no. E60749
Part # | AWG Size | No. of Cond. |
Nom. Jacket Thickness |
Nom. O.D. | Lbs./M’ |
1AS11402 | 14 | 2 | .045” | .325” | 78 |
1AS11403 | 14 | 3 | .045” | .340” | 84 |
1AS11404 | 14 | 4 | .045” | .375” | 104 |
1AS11405 | 14 | 5 | .045” | .410” | 127 |
1AS11406 | 14 | 6 | .045” | .440” | 147 |
1AS11407 | 14 | 7 | .045” | .475” | 165 |
1AS11408 | 14 | 8 | .045” | .510” | 200 |
1AS11409 | 14 | 9 | .060” | .580” | 235 |
1AS11410 | 14 | 10 | .060” | .590” | 246 |
1AS11411 | 14 | 11 | .060” | .605” | 270 |
1AS11412 | 14 | 12 | .060” | .605” | 290 |
1AS11413 | 14 | 13 | .060” | .635” | 305 |
1AS11414 | 14 | 14 | .060” | .635” | 325 |
1AS11415 | 14 | 15 | .060” | .665” | 340 |
1AS11416 | 14 | 16 | .060” | .665” | 354 |
1AS11417 | 14 | 17 | .060” | .725” | 400 |
1AS11418 | 14 | 18 | .060” | .725” | 410 |
1AS11419 | 14 | 19 | .060” | .725” | 430 |
1AS11421 | 14 | 21 | .060” | .740” | 470 |
1AS11424 | 14 | 24 | .060” | .820” | 510 |
1AS11425 | 14 | 25 | .080” | .875” | 520 |
1AS11430 | 14 | 30 | .080” | .905” | 660 |
1AS11437 | 14 | 37 | .080” | .990” | 785 |