FLEXIBLE AND PORTABLE CORD, Small Diameter Control
SDN - UL Type TC
90°C - 600 Volt


CONSTRUCTION
Conductor: - Bare, soft annealed copper per ASTM B-3
- 14 AWG (19 strand)
Insulation: - Each conductor is concentrically insulated with a 15 mil wall of high dielectric flame retardant polymer with 5 mil wall of clear polymide (nylon) jacket extruded over primary insulation and conforming to UL requirements
Cabling: - The applicable number of conductors are cabled together with fillers as necessary with a suitable layer
- A clear mylar tape is helically applied over the core
Color Code Chart 107:
Cond. Num. Color Cond. Num. Color
1 Black 2 Red
3 Blue 4 Orange
5 Yellow 6 Brown
7 Red w/ Black Stripe 8 Blue w/ Black Stripe
9 Orange w/ Black Stripe 10 Yellow w/ Black Stripe
11 Brown w/ Black Stripe 12 Black w/ Red Stripe
13 Blue w/ Red Stripe 14 Orange w/ Red Stripe
15 Yellow w/ Red Stripe 16 Brown w/ Red Stripe
17 Black w/ Blue Stripe 18 Red w/ Blue Stripe
19 Orange w/ Blue Stripe 20 Yellow w/ Blue Stripe
21 Brown w/ Blue Stripe 22 Black w/ Orange Stripe
23 Red w/ Orange Stripe 24 Blue w/ Orange Stripe
25 Yellow w/ Orange Stripe 26 Brown w/ Orange Stripe
27 Black w/ Yellow Stripe 28 Red w/ Yellow Stripe
29 Blue w/ Yellow Stripe 30 Orange w/ Yellow Stripe
31 Brown w/ Yellow Stripe 32 Black w/ Brown Stripe
33 Red w/ Brown Stripe 34 Blue w/ Brown Stripe
35 Orange w/ Brown Stripe 36 Yellow w/ Brown Stripe
37 Black
Overall Jacket: - Gas/vapor-tight heavy duty, flame and oil resistant neoprene (black) per UL-1277 and ICEA S-73-532 part 4
Applications:
- To be installed in trays, raceways, troughs, channels, ducts, conduit, and by direct burial
- Recommended for wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required
- Designed for control, power, lighting, telemetering, signal, relay traffic control, wherever flexible, small diameter cable is required such as cranes, hoists, and some robotics applications
- Cables can be flexed at -40°C
Standards:
- OSHA acceptable
- Recognized for use in Class 1 or 2, Division 2 hazardous locations
- UL Type power and control tray cables and Articles 318, 340, 500, and 501 of the NEC
- Cables pass UL 1277 and IEEE 383 (70,000 BTU) flame tests
- Cables are rated 600 volts, 90°C dry and 75°C wet. UL file no. E60749
Part # AWG Size No. of
Cond.
Nom. Jacket
Thickness
Nom. O.D. Lbs./M’
1AS11402 14 2 .045” .325” 78
1AS11403 14 3 .045” .340” 84
1AS11404 14 4 .045” .375” 104
1AS11405 14 5 .045” .410” 127
1AS11406 14 6 .045” .440” 147
1AS11407 14 7 .045” .475” 165
1AS11408 14 8 .045” .510” 200
1AS11409 14 9 .060” .580” 235
1AS11410 14 10 .060” .590” 246
1AS11411 14 11 .060” .605” 270
1AS11412 14 12 .060” .605” 290
1AS11413 14 13 .060” .635” 305
1AS11414 14 14 .060” .635” 325
1AS11415 14 15 .060” .665” 340
1AS11416 14 16 .060” .665” 354
1AS11417 14 17 .060” .725” 400
1AS11418 14 18 .060” .725” 410
1AS11419 14 19 .060” .725” 430
1AS11421 14 21 .060” .740” 470
1AS11424 14 24 .060” .820” 510
1AS11425 14 25 .080” .875” 520
1AS11430 14 30 .080” .905” 660
1AS11437 14 37 .080” .990” 785
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.