CONSTRUCTION | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Conductor: | - Bare, soft annealed copper per ASTM B-3 - 16 AWG (19 strand) |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Insulation: | - Each conductor is concentrically insulated with a 15 mil wall of high dielectric flame retardant polymer with 5 mil wall of clear polymide (nylon) jacket extruded over primary insulation and conforming to UL requirements | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cabling: | - The applicable number of conductors are cabled together with fillers as necessary with a suitable layer - A clear mylar tape is helically applied over the core |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Color Code Chart 107: |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Overall Jacket: | - Gas/vapor-tight heavy duty, flame and oil resistant neoprene (black) per UL-1277 and ICEA S-73-532 part 4 |
Applications:
- To be installed in trays, raceways, troughs, channels, ducts, conduit, and by direct burial
- Recommended for wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required
- Designed for control, power, lighting, telemetering, signal, relay traffic control, wherever flexible, small diameter cable is required such as cranes, hoists, and some robotics applications.
- Cables can be flexed at -40°C
Standards:
- Recommended for wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required
- Designed for control, power, lighting, telemetering, signal, relay traffic control, wherever flexible, small diameter cable is required such as cranes, hoists, and some robotics applications.
- Cables can be flexed at -40°C
- OSHA acceptable
- Recognized for use in Class 1 or 2, Division 2 hazardous locations
- UL Type power and control tray cables and Articles 318, 340, 500, and 501 of the NEC
- Cables pass UL 1277 and IEEE 383 (70,000 BTU) flame tests
- Cables are rated as Type TC, 600 volts, 90°C
- Recognized for use in Class 1 or 2, Division 2 hazardous locations
- UL Type power and control tray cables and Articles 318, 340, 500, and 501 of the NEC
- Cables pass UL 1277 and IEEE 383 (70,000 BTU) flame tests
- Cables are rated as Type TC, 600 volts, 90°C
Part # | AWG Size | No. of Cond. |
Nom. Jacket Thickness |
Nom. O.D. | Lbs./M’ |
1AS11602 | 16 | 2 | .045” | .295” | 51 |
1AS11603 | 16 | 3 | .045 | .305” | 62 |
1AS11604 | 16 | 4 | .045” | .335” | 77 |
1AS11605 | 16 | 5 | .045” | .360” | 92 |
1AS11606 | 16 | 6 | .045” | .390” | 107 |
1AS11607 | 16 | 7 | .045” | .415” | 123 |
1AS11608 | 16 | 8 | .045” | .450” | 137 |
1AS11609 | 16 | 9 | .045” | .480” | 165 |
1AS11610 | 16 | 10 | .045” | .490” | 165 |
1AS11611 | 16 | 11 | .045” | .500” | 180 |
1AS11612 | 16 | 12 | .045” | .500” | 188 |
1AS11613 | 16 | 13 | .060” | .555” | 225 |
1AS11614 | 16 | 14 | .060” | .555” | 240 |
1AS11615 | 16 | 15 | .060” | .590” | 255 |
1AS11616 | 16 | 16 | .060” | .590” | 258 |
1AS11617 | 16 | 17 | .060” | .630” | 290 |
1AS11618 | 16 | 18 | .060” | .630” | 290 |
1AS11619 | 16 | 19 | .060” | .630” | 296 |
1AS11621 | 16 | 21 | .060” | .650” | 340 |
1AS11624 | 16 | 24 | .060” | .715” | 367 |
1AS11625 | 16 | 25 | .060” | .730” | 380 |
1AS11630 | 16 | 30 | .060” | .750” | 432 |
1AS11637 | 16 | 37 | .080” | .870” | 556 |
1AS11660 | 16 | 60 | .080” | 1.05” | 953 |