INSTRUMENTATION CABLE, PVIC™* - Multiple Pairs
Overall Shield - PLTC/ITC
105°C - 300 Volt


CONSTRUCTION
Conductor: - Annealed Bare Copper
- 7 Strands Class B
Insulation: - Polyvinyl Chloride (PVC)
- Black & white numbered
Shield: - Aluminum Mylar Tape - 100% coverage
Drain Wire: - 7 Strand Tinned Copper
Color Code Chart:
Type Color
Pairs Black, White & Numbered
Jacket: - Black Polyvinyl Chloride (PVC)
Standards:
- UL listed as type PLTC & CL3 per UL standard 13 and as type ITC per UL standard 2250
- Meets IEEE 1202 flame test
- All materials used in the manufacture of this cable are RoHS compliant
Applications:
- Cable is suitable for use in Class I Division II hazardous locations
- Cable is UL approved for Sunlight Resistant and Direct Burial Applications
Part # AWG Size No. of Pairs Nom. Insul. Thick. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
1L11824 18 24 .016” .070” .884” 492 TCF100100A
Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager.