INSTRUMENTATION CABLE, PVIC™* - Multiple Triads
Individual and Overall Shield
105°C - 300 Volt - PLTC/ITC


CONSTRUCTION
Conductor: - 7 strand bare copper
Insulation: - PVC
Individual Shield: - Aluminum/polyester tape
Drain Wire: - Stranded, tinned copper
Overall Shield: - Aluminum/polyester tape
Drain Wire: - Stranded, tinned copper
Color Code Chart:
Type Color
Triads Black, White, Red & Numbered
Jacket: - Sunlight resistant Polyvinyl Chloride (PVC)
Applications:
- Process instrumentation requiring multi-pairs Power Limited Tray Cable & Instrumentation Tray Cable (ITC)
- Acceptable in Class 1 Division 2 hazardous areas per NEC Article 501-4(b) for UL Type PLTC/ITC cables
Standards:
- UL Type PLTC/ITC - 300 Volt
-IEEE 383 Flame Test (70,000 BTU/hr)
- UL Listed Subject 13 (70,000 BTU/hr) for PLTC
- UL Listed Subject 2250 (70,000 BTU/hr) for ITC
- OSHA Acceptable
Part # AWG Size No. of Triads Nom. Insul. Thick. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
1L61802 18 2 .015” .040” .321” 77 TCF05040A
1L61804 18 4 .015” .050” .444” 143 TCF05054A
1L61808 18 8 .015” .060” .691” 275 TCF05078A
1L61812 18 12 .015” .060” .840” 412 TCF07588A
1L61816 18 16 .015” .070” .960” 550 TCF100100A
1L61820 18 20 .015” .070” 1.06” 668 TCF125109A
1L61824 18 24 .015” .070” 1.15” 785 TCF125128A
1L61836 18 36 .015” .080” 1.37” 1151 TCF125147A
Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager.