TRAY CABLE, CVTC™* - XHHW-2 Insulation
PVC Jacket - UL Type TC
90°C - 600
ER Rated


CONSTRUCTION
Conductor: - Stranded bare copper Class B per ASTM B-3
Insulation: - Flame-retardant cross-linked polyethylene meeting the requirements for XHHW-2 per UL 44 and the requirements of ICEA S-66-524 for XLPE insulation as standard
Assembly: - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary
- A binder tape (when required) of synthetic material assembles the core in a tight circular configuration
Color Code Chart 107 (E-2):
Cond. Num. Color Cond. Num. Color
1 Black 2 Red
3 Blue 4 Orange
5 Yellow 6 Brown
7 Red w/ Black Stripe 8 Blue w/ Black Stripe
9 Orange w/ Black Stripe 10 Yellow w/ Black Stripe
11 Brown w/ Black Stripe 12 Black w/ Red Stripe
Jacket: - Black sunlight resistant, flame retardant polyvinyl chloride per UL 1277 requirements for Type TC power and control cables
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for class 1 Division 2 hazardous locations as per NEC
Standards:
- UL Type TC, 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
- Meets cold bend test of -25*C per UL 1277
- Type TC-ER on constructions greater than 2 conductors
Part # AWG Size No. of Cond. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
1A51002* 10 2 Flat .045” .290” x .480” 114 -
1A51002R* 10 2 .045” .455” 130 TCF07554A
1A51003 10 3 .045” .485” 173 TCF07554A
1A51004 10 4 .060” .560” 236 TCF07567A
1A51005 10 5 .060” .615” 287 TCF07567A
1A51007 10 7 .060” .670” 371 TCF07578A
1A51009 10 9 .060” .785” 479 TCF10088A
1A51012 10 12 .080” .920” 644 TCF100100A
1A51014 10 14 .080” 1.05” 809 TCF100109A
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.
*ER Rating only applies to 3 conductors or more