TRAY CABLE, XHHW-2 Insulation
PVC Jacket - 90°C - 600 Volt
UL Type TC - with Ground
ER Rated


CONSTRUCTION
Conductor: - Class B stranded soft drawn bare copper per ASTM B-3 & B-8
Insulation: - Flame-retardant cross-linked polyethylene meeting the requirements for XHHW-2 per UL 44 and the requirements of ICEA S-66-524 for XLPE insulation as standard
Ground Conductor: - Stranded bare copper per UL 1277
Assembly: - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary.
- The length of lay shall be per Table 9.1 of UL 1277
- A binder tape (when required) of synthetic material assembles the core in a tight circular configuration
Color Code Chart 108:
Cond. Num. Cond. Marking Cond. Num. Cond. Marking
1 "1" One 2 "2" Two
3 "3" Three 4 "4" Four
Jacket: - Black sunlight resistant 90°C Polyvinyl Chloride (PVC) material meeting the requirements of Clause 10.17 from UL 1277
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial and for Class 1 Division 2 hazardous locations as per NEC
Standards:
- UL Type TC 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-95-658/NEMA WC70
- ICEA T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
- Meets cold bend test of -25*C per UL 1277
Part # AWG Size No. of Cond. Nom. Jacket Thick. Grd. Size Nom. O.D. Lbs./M’ Recommended Fitting
1A60804 8 4 .060” 10 .725” 416 TCF07578A
1A60604 6 4 .060” 8 .820” 594 TCF10088A
1A60404 4 4 .080” 8 .975” 872 TCF100100A
1A60204 2 4 .080” 6 1.12” 1284 -
1A61/004 1/0 4 .080” 6 1.37” 1910 TCF150140A
1A62/004 2/0 4 .080” 6 1.48” 2311 TCF150165A
1A64/004 4/0 4 .110” 4 1.81” 3598 TCF200186A
1A625004 250 4 .110” 4 1.97” 4213 TCF200219A
1A635004 350 4 .110” 3 2.23” 5686 4-300TC
1A650004 500 4 .110” 2 2.56” 7869 4-300TC
1A675004 750 4 .140” 1 3.14” 11495 4-350TC
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.