CONSTRUCTION | |||||||||||||||||||||
Conductor: | - Stranded soft drawn tinned copper, Class B | ||||||||||||||||||||
Insulation: | - Flame retardant ethylene propylene rubber meeting the requirements for EPR VW-1 per UL | ||||||||||||||||||||
Assembly: | - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary - A binder tape (when required) of synthetic material assembles the core in a tight circular configuration | ||||||||||||||||||||
Color Code Chart 106: |
|
||||||||||||||||||||
Jacket: | - Black sunlight resistant thermoplastic Chlorinated Polyethylene (CPE) |
Applications:
Standards:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
- UL Type TC 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-95-658 / NEMA WC70
- ICEA-T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
Part # | AWG Size | No. of Cond. | Nom. Insul. Thick. | Nom. Jacket Thick. | Nom. O.D. | Lbs./M”“ | Chart Reference | Recommended Fitting |
1AF161202* | 12 | 2 | .030” | .045” | .250” x .410” | 95 | Chart 106 | |
1AF161203 | 12 | 3 | .030” | .045” | .430” | 120 | Chart 106 | TCF05054A |
1AF161204 | 12 | 4 | .030” | .045” | .470” | 150 | Chart 106 | TCF05054A |
1AF161205 | 12 | 5 | .030” | .045” | .495” | 180 | Chart 106 | TCF05054A |
1AF161207 | 12 | 7 | .030” | .060” | .600” | 250 | Chart 106 | TCF05067A |
1AF161212 | 12 | 12 | .030” | .060” | .750” | 410 | Chart 106 | TCF05078A |
*ER Rating only applies to 3 conductors or more