TRAY CABLE, VNTC®* - PVC Jacket
PVC/Nylon Insulation
90°C - 600 Volt - UL Type TC
ER Rated


CONSTRUCTION
Conductor: - Stranded bare copper Class B per UL 83
Insulation: - Extruded polyvinyl chloride to UL requirements for Class THHN and THWN insulation, which with nylon jacket is approved for Type THHN and THWN wires per UL 83
- 14 & 12 AWG - Insulation thickness .015", Nylon thickness .004"
- 10 AWG - Insulation thickness .020", Nylon thickness .005"
Assembly: - The conductors are cabled with fillers where needed to make a round compact core and a suitable tape is applied over the construction
Color Code Chart 106:
Cond. Num. Color Cond. Num. Color
1 Black 2 White
3 Red 4 Green
Color Code Chart 107:
Cond. Num. Color Cond. Num. Color
1 Black 2 Red
3 Blue 4 Orange
5 Yellow 6 Brown
7 Red w/ Black Stripe 8 Blue w/ Black Stripe
9 Orange w/ Black Stripe 10 Yellow w/ Black Stripe
11 Brown w/ Black Stripe 12 Black w/ Red Stripe
13 Blue w/ Red Stripe 14 Orange w/ Red Stripe
15 Yellow w/ Red Stripe 16 Brown w/ Red Stripe
17 Black w/ Blue Stripe 18 Red w/ Blue Stripe
19 Orange w/ Blue Stripe 20 Yellow w/ Blue Stripe
21 Brown w/ Blue Stripe 22 Black w/ Orange Stripe
23 Red w/ Orange Stripe 24 Blue w/ Orange Stripe
25 Yellow w/ Orange Stripe 26 Brown w/ Orange Stripe
27 Black w/ Yellow Stripe 28 Red w/ Yellow Stripe
29 Blue w/ Yellow Stripe 30 Orange w/ Yellow Stripe
31 Brown w/ Yellow Stripe 32 Black w/ Brown Stripe
33 Red w/ Brown Stripe 34 Blue w/ Brown Stripe
35 Orange w/ Brown Stripe 36 Yellow w/ Brown Stripe
37 Black
Jacket: - Black sunlight resistant, flame retardant polyvinyl chloride per UL 1277 requirements for Type TC power and control cables
Applications:
- Control circuits for operation and interconnection of protective and signaling devices, and for general use in manufacturing, industrial and commercial distribution systems
- UL listed and labeled for installation in ladders, troughs, channels, solid bottom trays and other similar structures (NEC Articles 318 and 340), and in duct, conduit, wireways and all other installations approved for building wire
- In hazardous locations per NEC Articles 500 and 501. May be used in wet or dry locations, sunlight resistant, and suitable for direct burial
Standards:
- UL Type TC, 600 Volt
- NEC Type TFN Conductors
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
- Extended Run Rated
Part # AWG Size No. of Cond. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Chart Reference Recommended Fitting
1A11202F* 12 2 .045” .260” x .360” 83 Chart 107 -
1A11202R* 12 2 .045” .355” 85 Chart 107 -
1A11203 12 3 .045” .385” 110 Chart 107 TCF07540A
1A11204 12 4 .045” .420” 138 Chart 107 TCF05054A
1A11205 12 5 .045” .445” 165 Chart 107 TCF05054A
1A11206 12 6 .045” .495” 195 Chart 107 TCF05054A
1A11207 12 7 .045” .500” 217 Chart 107 TCF05054A
1A11209 12 9 .060” .615” 297 Chart 107 TCF05067A
1A11210 12 10 .060” .665” 325 Chart 107 TCF05067A
1A11212 12 12 .060” .685” 377 Chart 107 TCF07578A
1A11215 12 15 .060” .765” 475 Chart 107 TCF07578A
1A11216 12 16 .060” .765” 490 Chart 107 TCF07578A
1A11219 12 19 .060” .800” 568 Chart 107 TCF10088A
1A11220 12 20 .080” .895” 645 Chart 107 TCF100100A
1A11225 12 25 .080” .985” 775 Chart 107 TCF100100A
1A11230 12 30 .080” 1.04” 913 Chart 107 TCF100109A
1A11237 12 37 .080” 1.12” 1100 Chart 107 -

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.
*ER Rating only applies to 3 conductors or more