MEDIUM VOLTAGE POWER CABLE, 15kV-UNISHIELD®-EPR Insulation,CPE Jacket
MV-105-100% or 133% Insulation Level
Single Conductor


CONSTRUCTION
Conductor: - Annealed bare copper
- Anapact™ Compact, Class B stranding
Extruded Strand Shield (ESS) - Extruded thermoset semi-conducting stress control layer over conductor
Insulation: - Ethylene Propylene Rubber (EPR), colored to contrast with the black conducting shield layers
Composite Insulation Shield and Jacket: - Six corrugated copper drain wires embedded in a extruded black conducting flame-retardant Chlorinated Polyethylene (CPE) composite insulation shield and jacket
Applications:
- Suitable for use in wet or dry locations when installed in accordance with the NEC
- Suitable for use in aerial, direct burial, conduit, open tray, and underground duct installations
- For use in a broad range of commercial, industrial, and utility projects
Features:
- Flexibility for easy handling
- Meets Cold Bend Test at -55°C
- Reduced conductor size and shield system provides the smallest premium medium-voltage shielded, jacketed power cable with full insulation
- Smaller outside dimensions may reduce the size of duct needed or increase the ampacity per duct
- UL Listed as Type MV-105 for use in accordance with the NEC
- Sizes 1/0 AWG and larger are also listed and marked "For CT Use" in accordance with the NEC, and also meet IEEE 383 (70,000 BTU/hr
Temperature Ratings:
- Normal: 105°C
- Emergency: 140°C
- Short Circuit: 250°C
Standards:
- ICEA S-93-639/NEMA WC74 (formerly ICEA S-68-516 NEMA WC8)
- AEIC CS8 (formerly AEIC CS6)
Part # AWG No. of Strands Nominal Thickness Diameter Over Ins. Nom. O.D. Lbs./M’ Splices Available Terminations Available
Insulation Jacket
15kV – 100% Insulation Level
1MVU40201 2 7 .175” .080” .664” .841” 501 - -
1MVU41/001 1/0 19 .175” .080” .737” .916” 661 - -
1MVU42/001 2/0 19 .175” .080” .780” .960” 769 - -
1MVU44/001 4/0 19 .175” .080” .880” 1.07” 1079 - -
1MVU425001 250 37 .175” .080” .935” 1.13” 1232 - -
1MVU435001 350 37 .175” .085” 1.03” 1.23” 1613 - -
1MVU450001 500 37 .175” .085” 1.16” 1.36” 2149 - -
1MVU475001 750 61 .175” .100” 1.34” 1.56” 3064 - -
1MVU4100001 1000 61 .175” .100” 1.50” 1.72” 3936 - -
15kV – 133% Insulation Level
1MVU20201 2 7 .220” .080” .755” .937” 574 Cold-Heat Cold In/Out
Heat In/Out
1MVU21/001 1/0 19 .220” .080” .828” 1.02” 753 - -
1MVU22/001 2/0 19 .220” .080” .871” 1.07” 867 - -
1MVU24/001 4/0 19 .220” .080” .971” 1.17” 1171 Cold-Heat Cold In/Out
Heat In/Out
1MVU225001 250 37 .220” .085” 1.03” 1.24” 1349 - -
1MVU235001 350 37 .220” .085” 1.12” 1.33” 1720 - -
1MVU250001 500 37 .220” .085” 1.25” 1.46” 2267 Cold-Heat Cold In/Out
Heat In/Out
1MVU275001 750 61 .220” .100” 1.43” 1.67” 3216 - -
1MVU2100001 1000 61 .220” .115” 1.59” 1.86” 4164 - -
Note: The data shown is approximate and subject to standard industry and manufacturer tolerances.