CONSTRUCTION | |
Conductor: | - Annealed bare copper - Anapact™ Compact, Class B stranding |
Extruded Strand Shield (ESS): | - Extruded thermoset semiconducting stress control layer over conductor |
Insulation: | - Ethylene Propylene Rubber (EPR), colored to contrast with the black conducting shield layer |
Composite Insulation Shield and Jacket: | - Six corrugated copper drain wires embedded in an extruded black conducting flame-retardant Chlorinated Polyethylene (CPE) composite insulation shield and jacket |
Applications:
- Suitable for use in wet or dry locations when installed in accordance with NEC
- Suitable for use in aerial, direct burial, conduit, open tray, and underground duct installations
- For use in broad range of commercial, industrial, and utility projects
Features:
- Suitable for use in aerial, direct burial, conduit, open tray, and underground duct installations
- For use in broad range of commercial, industrial, and utility projects
- Flexibility for easy handling
- Meets Cold Bend Test at -55°C
- Reduced conductor size and shield system provides the smallest premium medium-voltage shielded, jacketed power cable with full insulation
- Smaller outside dimensions may reduce the size of duct needed or increase the ampacity per duct
- All features attribute to the fastest and easiest to install
- UL Listed as Type MV-90 for use in accordance with the NEC
- Sizes 1/0 AWG and larger are listed and marked "For CT Use" in accordance with the NEC, and also meet IEEE 383 (70,000 BTU/hr)
- Temperature Rating: 105°C
Standards:
- Meets Cold Bend Test at -55°C
- Reduced conductor size and shield system provides the smallest premium medium-voltage shielded, jacketed power cable with full insulation
- Smaller outside dimensions may reduce the size of duct needed or increase the ampacity per duct
- All features attribute to the fastest and easiest to install
- UL Listed as Type MV-90 for use in accordance with the NEC
- Sizes 1/0 AWG and larger are listed and marked "For CT Use" in accordance with the NEC, and also meet IEEE 383 (70,000 BTU/hr)
- Temperature Rating: 105°C
- ICEA S-93-639/NEMA WC 74 (formerly ICEA S-68-516/NEMA W)
- AEIC CS8 (formerly AEIC CS6)
- AEIC CS8 (formerly AEIC CS6)
Part # | AWG | No. of Strands | Nominal Thickness | Diameter Over Ins. | Nom. O.D. | Lbs./M’ | Splices Available | Terminations Available | |
Insulation | Jacket | ||||||||
1MVU10201 | 2 | 7 | .115” | .075” | .542” | .712” | 411 | Cold-Heat | Cold-Heat |
1MVU11/001 | 1/0 | 19 | .115” | .075” | .615” | .787” | 563 | - | - |
1MVU12/001 | 2/0 | 19 | .115” | .080” | .658” | .837” | 675 | - | - |
1MVU14/001 | 4/0 | 19 | .115” | .080” | .759” | .941” | 961 | Cold-Heat | Cold-Heat |
1MVU125001 | 250 | 37 | .115” | .080” | .813” | 1.00” | 1122 | - | - |
1MVU135001 | 350 | 37 | .115” | .080” | .909” | 1.11” | 1476 | - | - |
1MVU150001 | 500 | 37 | .115” | .085” | 1.03” | 1.24” | 2015 | Cold-Heat | Cold-Heat |
1MVU175001 | 750 | 61 | .115” | .085” | 1.22” | 1.48” | 2893 | - | - |
1MVU1100001 | 1000 | 61 | .115” | .100” | 1.38” | 1.61” | 3786 | - | - |