MEDIUM VOLTAGE POWER CABLE, Nonshielded - 2.4kV - EPR Insulation
PVC Jacket
MV-90


CONSTRUCTION
Conductor: - Compressed class B stranded tinned copper
Conductor Shield: - Nylon semi-conducting tape
Insulation: - 90°C rated Ethylene Propylene Rubber (EPR)
Jacket: - Extruded sunlight resistant PVC jacket
Applications:
  • UL listed
  • OSHA acceptable
  • Suitable for use in wet or dry locations at maximum operating temperature of 90°C for normal operation; 130°C for emergency overload conditions; and 250°C for short circuit conditions
  • May be installed in conduit, duct or aerially when properly supported by a messenger
Standards:
  • ICEA S-96-659
  • UL-1072
  • 2,400 Volts
  • Article 328 and 310
  • MV-90
Part # AWG Size No. of Strands Nom. Cond. Diameter Min. Avg. Insul. Wall Nom. O.D. Lbs/M Amps Splice Termination
1MVE10601 6 7 .181” .125” .605” 231 75 Heat Specs Cold Specs-Heat Specs
1MVE10401 4 7 .228” .125” .650” 296 97 Heat Specs Cold Specs-Heat Specs
1MVE10201 2 7 .287” .125” .710” 396 130 Heat Specs Cold Specs-Heat Specs
1MVE10101 1 19 .327” .125” .750” 465 155    
1MVE11/001 1/0 19 .367” .125” .790” 548 180 Heat Specs Cold Specs-Heat Specs
1MVE12/001 2/0 19 .412” .125” .835” 646 205 Heat Specs Cold Specs-Heat Specs
1MVE14/001 4/0 19 .520” .125” .975” 959 280 Heat Specs Cold Specs-Heat Specs
1MVE125001 250 37 .566” .140” 1.08” 1153 315 Heat Specs Cold Specs-Heat Specs
1MVE135001 350 37 .670” .140” 1.18” 1512 385 Heat Specs Cold Specs-Heat Specs
1MVE150001 500 37 .800” .140” 1.32” 2103 475    
1MVE175001 750 61 .983” .155” 1.55” 2971 600    
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.