MOTOR LEAD WIRE, SRML - SF-2
600 Volt
150°C & 200°C


CONSTRUCTION
Conductor: - Flexible stranded tinned copper
Insulation: - Silicone rubber
Jacket: - Fiber Glass Braid
- Color: Black
Applications:
- Used in wiring of electrical equipment in hazardous locations where exposure to temperature does not exceed 200°C.
- Class H stranding provides excellent flexibility for applications where temperature resistance and flexibility are necessary.
Standards:
- UL style: 3278, 3231
- 8 AWG and 6 AWG are CSA certified as equipment wire (SEWF-2)
- 4 AWG through 4/0 are CSA certified as equipment wire (SEW-2)
Part # AWG Size Stranding Nom. Insul. Thick. Braid Nom. O.D. Lbs./M’
1C50801 8   133   .060”   .005” .315”   91  
1C50601 6   133   .060”   .005” .355”   135  
1C50401 4   133   .060”   .005” .410”   196  
1C50201 2   133   .060”   .005” .475”   288  
1C50101 1   259   .080”   .005” .585”   359  
1C51/001 1/0   259   .080”   .007” .610”   468  
1C52/001 2/0   259   .080”   .007” .655”   545  
1C53/001 3/0   259   .080”   .007” .728”   660  
1C54/001 4/0   259   .080”   .007” .802”   820  
1C525001* 250   427   .095”   .040” .890”   985  
1C535001* 350   427   .095”   .040” 1.03”   1330  
1C550001* 500   427   .095”   .040” 1.18”   1885  
1C575001* 750   703   .110”   .040” 1.49”   2715  
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.

8 AWG and 6 AWG are 150°C UL (200°C Non-UL)

4 AWG and larger are 200°C UL

* Constructed with K fiber, UL 3410, CSA: AWM Class !, Group A/B. Other sizes available with K fiber also.

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.