TRAY CABLE, CVTC™* - XHHW-2 Insulation
PVC Jacket - UL Type TC
90°C - 600
ER Rated


CONSTRUCTION
Conductor: - Stranded bare copper Class B per ASTM B-3
Insulation: - Flame-retardant cross-linked polyethylene meeting the requirements for XHHW-2 per UL 44 and the requirements of ICEA S-66-524 for XLPE insulation as standard
Assembly: - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary
- A binder tape (when required) of synthetic material assembles the core in a tight circular configuration
Color Code Chart 107:
Cond. Num. Color Cond. Num. Color
1 Black 2 Red
3 Blue 4 Orange
5 Yellow 6 Brown
7 Red w/ Black Stripe 8 Blue w/ Black Stripe
9 Orange w/ Black Stripe 10 Yellow w/ Black Stripe
11 Brown w/ Black Stripe 12 Black w/ Red Stripe
13 Blue w/ Red Stripe 14 Orange w/ Red Stripe
15 Yellow w/ Red Stripe 16 Brown w/ Red Stripe
17 Black w/ Blue Stripe 18 Red w/ Blue Stripe
19 Orange w/ Blue Stripe 20 Yellow w/ Blue Stripe
21 Brown w/ Blue Stripe 22 Black w/ Orange Stripe
23 Red w/ Orange Stripe 24 Blue w/ Orange Stripe
25 Yellow w/ Orange Stripe 26 Brown w/ Orange Stripe
27 Black w/ Yellow Stripe 28 Red w/ Yellow Stripe
29 Blue w/ Yellow Stripe 30 Orange w/ Yellow Stripe
31 Brown w/ Yellow Stripe 32 Black w/ Brown Stripe
33 Red w/ Brown Stripe 34 Blue w/ Brown Stripe
35 Orange w/ Brown Stripe 36 Yellow w/ Brown Stripe
37 Black
Jacket: - Black sunlight resistant, flame retardant polyvinyl chloride per UL 1277 requirements for Type TC power and control cables
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for class 1 Division 2 hazardous locations as per NEC
Standards:
- UL Type TC, 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
- Meets cold bend test of -25*C per UL 1277 Section 15
Part # AWG Size No. of Cond. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
1A51402F* 14 2 Flat .045” .260” x .400” 62 -
1A51402* 14 2 .045” .370” 73 TCF07540A
1A51403 14 3 .045” .390” 93 TCF07540A
1A51404 14 4 .045” .425” 116 TCF05054A
1A51405 14 5 .045” .465” 140 TCF05054A
1A51407 14 7 .045” .505” 176 TCF05054A
1A51409 14 9 .060” .620” 245 TCF05067A
1A51412 14 12 .060” .700” 312 TCF07578A
1A51415 14 15 .060” .735” 386 TCF07578A
1A51419 14 19 .060” .815” 461 TCF07578A
1A51425 14 25 .080” .985” 641 TCF100100A
1A51430 14 30 .080” 1.05” 740 TCF100109A
1A51437 14 37 .080” 1.13” 888 -
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.