TRAY CABLE, FREP®* - XHHW-2 - (VW-1)
FR-EP Insulation - CPE Jacket
90°C - 600 Volt - UL Type TC
K-1 Color Code
ER Rated


CONSTRUCTION
Conductor: - Stranded soft drawn tinned copper, Class B
Insulation: - Flame retardant ethylene propylene rubber meeting the requirementsfor EPR VW-1 per UL
Assembly: - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary - A binder tape (when required) of synthetic material assembles the core in a tight circular configuration
Color Code Chart 106:
Cond. Num. Color Cond. Num. Color
1 Black 2 White
3 Red 4 Green
5 Orange 6 Blue
7 White w/ Black Stripe
Jacket: - Black sunlight resistant thermoplastic Chlorinated Polyethylene (CPE)
Applications:
  • Used as power and control cables in dry and wet locations
  • Can be installed in cable trays, raceways, and open air
  • Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
Standards:
  • UL Type TC 600 Volt
  • UL Type XHHW-2, VW-1 Conductors
  • ICEA S-95-658 / NEMA WC70
  • ICEA-T-29-520 (210,000 BTU/hr)
  • IEEE 1202 (70,000 BTU/hr) / CSA FT4
  • IEEE 383 (70,000 BTU/hr)
  • UL Subject 1277 (70,000 BTU/hr)
Part # AWG Size No. of Cond. Nom. Insul. Thick. Nom. Jacket Thick. Nom. O.D. Lbs./M”“ Chart Reference Recommended Fitting
1AF161402* 14 2 .030” .045” .235” x .365” 70 Chart 106  
1AF161403 14 3 .030” .045” .390” 85 Chart 106 TCF05040A
1AF161404 14 4 .030” .045” .425” 105 Chart 106 TCF05054A
1AF161405 14 5 .030” .045” .445” 125 Chart 106 TCF05054A
1AF161407 14 7 .030” .045” .505” 173 Chart 106 TCF05054A
1AF161409 14 9 .030” .060” .620” 240 Chart 106 TCF05067A
1AF161412 14 12 .030” .060” .670” 295 Chart 106 TCF05078A
*AF161402 has flat construction.Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.

*ER Rating only applies to 3 conductors or more