TRAY CABLE, Unshielded Tray Cable
UL Type TC - 600 Volt
4 Control Conductors w/ 3 Power Conductors and Bare Ground
90°C/75°C wet rated
ER Rated


CONSTRUCTION
Conductor: - Stranded bare copper Class B per UL 83
Insulation: - Extruded polyvinyl chloride to UL requirements for Class THHN and THWN insulation, which with nylon jacket is approved for Type THHN and THWN wires per UL 83
- 14 & 12 AWG - Insulation thickness .015", Nylon thickness .004"
- 10 AWG - Insulation thickness .020", Nylon thickness .005"
Assembly: - The conductors are cabled with fillers where needed to make a round compact core and a suitable tape is applied over the construction
Color Code Chart 108:
Cond. Num. Color Cond. Num. Color
1 "1" One 2 "2" Two
3 "3" Three 4 "4" Four
Jacket: - Black sunlight resistant, flame retardant polyvinyl chloride per UL 1277 requirements for Type TC power and control cables
Applications:
- Control circuits for operation and interconnection of protective and signaling devices, and for general use in manufacturing, industrial and commercial distribution systems
- UL listed and labeled for installation in ladders, troughs, channels, solid bottom trays and other similar structures (NEC Articles 318 and 340), and in duct, conduit, wireways and all other installations approved for building wire
- In hazardous locations per NEC Articles 500 and 501. May be used in wet or dry locations, sunlight resistant, and suitable for direct burial
Standards:
- UL Type TC, 600 Volt
- NEC Type TFN Conductors
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
Part # Control Size-AWG Size Insulation Thickness Power Size-AWG Size Insulation Thickness Ground Size-AWG Size Jacket Thickness Nom. O.D. Lbs./M Recommended Fitting
1AC30203* 12 .004” 2 .007” 6 .080” 1.02” 1050 TCF125109A
1AC30403 12 .004” 4 .007” 6 .080” .890” 760 TCF100100A
1AC30603 12 .004” 6 .006” 8 .060” .720” 530 TCF05078A
1AC30803 12 .004” 8 .006” 8 .060” .675” 405 TCF05078A
1AC31003 14 .045” 10 .045” 10 .060” .575” 288 TCF05067A
1AC31203 14 .045” 12 .045” 12 .060” .515” 220 TCF05054A
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.

*ER Rating only applies to 3 conductors or more