XLPO-LSOH, Control Non-Shielded, 90°C, 600 Volt
UL Type TC-LS-ER*
E-2 Color Code


CONSTRUCTION
Conductor: - 10 AWG fully annealed stranded copper per ASTM B33
- Class B stranding per ASTM B8.
Insulation: - Cross-Linked Polyolefin (XLPO), flame retardant and Low-Smoke
- Color Code: Table E-2, no white or green
Jacket: - Low-Smoke, Zero halogen Polyolefin
- Flame retardant and Sunlight resistant.
Application:
- In free air, raceways, aerial or direct burial
- In wet or dry locations
- Class 1 Division 2
- Permitted for Exposed Runs in three or more conductors
Compliances:
- UL 44 Type XHHW-2
- UL 1277 Type TC-LS-ER
- UL 1581
- UL 1685
- ROHS Compliant
- OSHA acceptable
- EPA 40 CFR, Part 261
Part # AWG No. of Cond. Nom. Jkt. Thickness Nominal O.D. Lbs./M’ T&B Fitting
1AZ11002F* 10 2 – flat 0.045” .455” x .270” 113 -
1AZ11003 10 3 0.045” 0.485” 172 TCF05054A
1AZ11004 10 4 0.060” 0.560” 234 TCF05067A
1AZ11005 10 5 0.060” 0.615” 284 TCF05067A
1AZ11007 10 7 0.060” 0.670” 381 TCF07578A
1AZ11009 10 9 0.060” 0.760” 464 TCF07578A
1AZ11012 10 12 0.080” 0.905” 651 TCF100100A
Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager.