XLPO-LSZH, Control Non-Shielded, 90°C, 600 Volt
UL Type TC-LS-ER*
E-2 Color Code


CONSTRUCTION
Conductor: - 12 AWG fully annealed stranded copper per ASTM B33
- Class B stranding per ASTM B8
Insulation: - Cross-Linked Polyolefin (XLPO), flame retardant and Low-Smoke
- Color Code: Table E-2, no white or green
Jacket: - Low-Smoke, Zero halogen Polyolefin
- Flame retardant and Sunlight resistant
Application:
- In free air, raceways, aerial or direct burial
- In wet or dry locations
- Class 1 Division 2
- Permitted for Exposed Runs in three or more conductors
Compliances:
- UL 44 Type XHHW-2
- UL 1277 Type TC-LS-ER
- UL 1581
- UL 1685
- ROHS Compliant
- OSHA acceptable
- EPA 40 CFR, Part 261
Part # AWG No. of Cond. Nom. Jkt. Thickness Nominal O.D. Lbs./M’ T&B Fitting
1AZ11202F* 12 2 – flat 0.045” .400” x .245” 82 -
1AZ11203 12 3 0.045” 0.435” 124 TCF05054A
1AZ11204 12 4 0.045” 0.475” 157 TCF05054A
1AZ11205 12 5 0.045” 0.520” 191 TCF05054A
1AZ11207 12 7 0.060” 0.595” 268 TCF05067A
1AZ11209 12 9 0.060” 0.695” 337 TCF07578A
1AZ11212 12 12 0.060” 0.765” 428 TCF07578A
1AZ11219 12 19 0.060” 0.940” 688 TCF100100A
Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager.