CONSTRUCTION | |||||||||||||
Assembly: | - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary. - A binder tape of synthetic material assembles the core in a tight circular configuration. |
||||||||||||
Color Code Chart 107: |
|
||||||||||||
Conductor: | - Stranded soft drawn tinned copper, Class B. | ||||||||||||
Insulation: | - Flame retardant ethylene propylene rubber meeting the requirements for EPR VW-1 per UL. | ||||||||||||
Shield: | - Aluminum/polyester laminated shielding tape shall be applied helically over the conductors. Over the shield is a stranded tinned copper drain wire. | ||||||||||||
Jacket: | - Black sunlight resistant thermoplastic Chlorinated Polyethylene (CPE) |
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air.
- Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
* ER Rating only applies to 3 conductors or more
Standards:
- Can be installed in cable trays, raceways, and open air.
- Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
* ER Rating only applies to 3 conductors or more
- UL Type TC 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-82-552 - 600 Volt
- ICEA T-29-520 (210,000 BTU/hr.)
- IEEE 1202 (70,000 BTU/hr.)/CSA FT4
- IEEE 383 (70,000 BTU/hr.)
- UL Subject 1277 (70,000 BTU/hr)
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-82-552 - 600 Volt
- ICEA T-29-520 (210,000 BTU/hr.)
- IEEE 1202 (70,000 BTU/hr.)/CSA FT4
- IEEE 383 (70,000 BTU/hr.)
- UL Subject 1277 (70,000 BTU/hr)
Part # | AWG Size | No. of Cond. | Nom. Jacket Thick | Nom. O.D. | Lbs./M’ | Recommended Fitting |
1AF21802* | 18 | 2 | .045” | .300” | 45 | TCF05040A |
1AF21803 | 18 | 3 | .045” | .316” | 55 | TCF05040A |
1AF21602* | 16 | 2 | .045” | .324” | 52 | TCF05040A |
1AF21603 | 16 | 3 | .045” | .342” | 68 | TCF05040A |
1AF21604 | 16 | 4 | .045” | .480” | 95 | TCF05054A |