SHIELDED TRAY CABLE, VNTC®* - PVC Jacket
PVC/Nylon Insulation 90°C
600 Volt - UL Type TC
ER Rated


CONSTRUCTION
Conductor: - Stranded bare copper Class B per UL 62
Insulation: - Extruded polyvinyl chloride to UL requirements for Class TFN and TFFN insulation with nylon jacket is approved per UL 83
- Insulation Thickness: .015", Nylon Thickness: .004"
Shield: - 100% aluminum polyester with tinned copper drain wire
Assembly: - The conductors are cabled with fillers where needed to make a round compact core and a suitable tape (when required) is applied over the construction
Color Code Chart 107:
Cond. Num. Color Cond. Num. Color
1 Black 2 Red
3 Blue 4 Orange
5 Yellow 6 Brown
7 Red w/ Black Stripe 8 Blue w/ Black Stripe
9 Orange w/ Black Stripe 10 Yellow w/ Black Stripe
11 Brown w/ Black Stripe 12 Black w/ Red Stripe
13 Blue w/ Red Stripe 14 Orange w/ Red Stripe
15 Yellow w/ Red Stripe 16 Brown w/ Red Stripe
17 Black w/ Blue Stripe 18 Red w/ Blue Stripe
19 Orange w/ Blue Stripe 20 Yellow w/ Blue Stripe
21 Brown w/ Blue Stripe 22 Black w/ Orange Stripe
23 Red w/ Orange Stripe 24 Blue w/ Orange Stripe
25 Yellow w/ Orange Stripe 26 Brown w/ Orange Stripe
27 Black w/ Yellow Stripe 28 Red w/ Yellow Stripe
29 Blue w/ Yellow Stripe 30 Orange w/ Yellow Stripe
31 Brown w/ Yellow Stripe 32 Black w/ Brown Stripe
33 Red w/ Brown Stripe 34 Blue w/ Brown Stripe
35 Orange w/ Brown Stripe 36 Yellow w/ Brown Stripe
37 Black
Jacket: - Black sunlight resistant, flame retardant polyvinyl chloride per UL 1277 requirements for Type TC power and control cables
Applications:
- Control circuits for operation and interconnection of protective and signaling devices, and for general use in manufacturing, industrial, and commercial distribution systems
- UL listed and labeled for installation in ladders, trough, channels, solid bottom trays and other similar structures (NEC Articles 318 and 340), and in duct, conduit, and wireways
- In hazardous locations per NEC Articles 500 and 501. May be used in wet or dry locations, sunlight resistant, and suitable for direct burial
Standards:
- UL Type TC, 600 Volt
- NEC Type TFN conductors
- IEEE 1202 (70,000 BTU/hr)/CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
Part # AWG Size No. of Cond. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fittings
1A21602 16 2 .045” .300” 52 TCF07540A
1A21603 16 3 .045” .320” 63 TCF07540A
1A21604 16 4 .045” .350” 77 TCF07540A
1A21605 16 5 .045” .370” 91 TCF07540A
1A21607 16 7 .045” .410” 119 TCF05054A
1A21609 16 9 .045” .470” 150 TCF05054A
1A21610 16 10 .045” .495” 168 TCF05054A
1A21612 16 12 .045” .510” 185 TCF05054A
1A21619 16 19 .060” .675” 300 TCF05067A
1A21625 16 25 .060” .727” 377 TCF07578A
1A21637 16 37 .080” .945” 595 TCF100100A
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.
*ER Rating only applies to 3 conductors or more